34
Sec. Description
Range
Default
U/M
TCIN Inactive time
1 ÷ 60
30
min
AH O Thermostat activation temperature
0 ÷ 95
40
°C
AH F Thermostat deactivation temperature
0 ÷ 95
45
°C
t1 O Thermostat activation time 1
00:00 ÷ 23:45
00:00
hh:mm
t1 F
Thermostat deactivation time 1
00:00 ÷ 23:45
00:00
hh:mm
t2 O Thermostat activation time 2
00:00 ÷ 23:45
00:00
hh:mm
t2 F Thermostat deactivation time 2
00:00 ÷ 23:45
00:00
hh:mm
t3 O Thermostat activation time 3
00:00 ÷ 23:45
00:00
hh:mm
t3 F Thermostat deactivation time 3
00:00 ÷ 23:45
00:00
hh:mm
OtD Anti-legionella function
ON - OFF
OFF
PDIS Monitoring period
0 to 30:0 to 24h
01:00
hh
TDIS Disinfection temperature
0 ÷ 95
60
°C
DDIS Disinfection duration
00:00 ÷ 23:59
01:00
hh:mm
SDIS Wait time
00:00 ÷ 24:00
00:00
hh:mm
GFD Grundfos Direct Sensor™ activation
OFF, 12, 40, 40F
OFF
OHQM Thermal energy metering
ON - OFF
OFF
PMAX Flow rate in l/min
0.5 ÷ 100
6
l/min
SEN Digital sensor for measuring flow rate
OFF, 1, 2
2
MEDT Type of frost protection
0 ÷ 3
1
MED% Level of frost protection
20 ÷ 70
45
%
ODB Drainback function
ON - OFF
OFF
tDTO Period – activation condition
1 ÷ 100
60
s
tFLL Filling time
1 ÷ 30
5
min
tSTB Stabilisation
1 ÷ 15
2
min
MAN1 Relay 1 manual mode
OFF, Auto, ON
Auto
MAN2 Relay 2 manual mode
OFF, Auto, ON
Auto
LANG Language
DE, EN, FR, ES, IT
DE
UNIT Unit of measurement for temperature
°F - °C
°C