When maximum storage cylinder temperature (
S MX
) is reached,
the solar pump stays on to stop the collector overheating.
Meanwhile, storage cylinder temperature may continue to rise,
but only to 95 °C (storage cylinder heating safety deactivation
temperature).
The solar pump stays on in the evening to cool the storage cyl-
inder through the collector. The pump remains on until storage
cylinder temperature falls below maximum temperature.
If domestic hot water is not drawn off for an extended period,
the supplementary holiday cooling function
OHOL
can be acti-
vated to increase storage cylinder cooling. If the
OHOL
function is
activated, temperature setting
THOL
replaces maximum storage
cylinder temperature (
S MX / S1MX
) as deactivation temperature
for the storage cylinder cooling function.
When the holiday cooling function is activated, the symbols
and
(flashing) appear on the display. When holiday cooling
is activated, the symbols
,
and
(flashing) appear on
the display.
19.12
Tube collector option
OTC
: Tube collector option
Setting range: ON, OFF
Default setting: OFF
TCST
: Tube collector function, activation time
Setting range: 00:00 ... 23:45
Default setting: 07:00
TCEN
: Tube collector option, deactivation time
Setting range: 00:00 ... 23:45
Default setting: 19:00
TCRU
: Tube collector option, run time
Setting range: 5 ... 500 s
Default setting: 30 s
TCIN
: Tube collector option, inactive time
Setting range: 1 ... 60 min
Default setting: 30 min
The tube collector function is activated during the set time band
(between
TCST
and
TCEN
). The function activates the solar pump
for the run time set in (
TCRU
) between the inactive times (set in
TCIN
) to compensate for the delay in measurement of collector
temperature.
If run time
TCRU
is set to more than ten seconds, the pump
functions at maximum speed for the first ten seconds (starting
power).
The pump runs at the minimum speed setting
nMN
for the re-
mainder of the set run time. This function is suppressed if the
collector sensor if faulty or the collector blocked.