6

Heating system:

-  open the automatic vent valves (

C - E

)

-  manually open the system drain valve (

B

)

-  drain from the lowest points of the system.

DHW system:

-  close the main water valve

-  unscrew the cap on the hose connector

-  connect a plastic hose to the connector of the boiler drain valve (

A

)

-  loosen the drain valve to open it

-  open the hot and cold water taps.

4 -  COMMISSIONING AND MAINTENANCE

4.1 

Preparation for initial commissioning

Before turning on and testing the boiler for the first time, check that:

-  the system gas and water valves are open

-  the type of gas and the supply pressure comply with the boiler 

specifications

-  the vent valve cap is open

-  the hydraulic circuit pressure, when cold, is between 1 and 1.5 bar 

and the circuit is de-aerated

-  preloading of the expansion tank is adequate (refer to the data 

table)

-  the electrical connections have been made correctly

-  the flue gas discharge ducts and the combustion air suction vents 

have been fitted correctly

-  that the pump rotates freely as deposits or residue may impair 

smooth rotation, especially after prolonged periods of disuse.

Releasing the pump shaft if necessary

-  Insert a screwdriver into hole (

1

) of the pump. 

-  Press (

a

) and turn the screwdriver (

b

) until the motor shaft releases.

1

a

b

  Take great care when carrying out this operation so as not to 

damage the components.

4.2 

First start-up

To turn on the boiler:

-  Connect the boiler to the mains

-  Open the gas valve, to enable the gas supply 

-  Adjust the room thermostat to the desired temperature (~20°C)

Turn the function selector to the required setting:

Winter

When the function selector is set to within this range, the boiler sup-

plies domestic hot water and heating. In the event of a heating re-

quest, the boiler turns on. The digital display indicates the heating 

water temperature. In the event of a DHW request, the boiler turns 

on. The display indicates the temperature of the domestic hot water.

WINTER MODE

Heating water temperature adjustment 

To adjust the temperature of the heating water, turn the function se-

lector within the adjustment range (clockwise to increase and anti-

clockwise to decrease).

HEATING WATER 

TEMPERATURE

DOMESTIC HOT WATER 

TEMPERATURE

Summer

By turning the function selector to the Summer symbol 

 the con-

ventional function of only DHW is activated. In the event of a DHW 

request, the boiler turns on. The digital display indicates the delivery 

temperature.

SUMMER MODE

DHW temperature adjustment 

To adjust the domestic hot water temperature (bathrooms, showers, 

kitchens, etc.), turn the dial with the symbol   clockwise to increase 

the value, or anti-clockwise to decrease (min. value 37°C - max. 

value 60°C). The boiler remains on standby until the burner ignites 

following a heat request. The boiler operates until the controlled tem-

peratures are reached or the heat demand is met, after which it re-

turns to standby status. In the case of a temporary stop, the digital 

display shows the code associated with the fault that has occurred.

DHW TEMPERATURE ADJUSTMENT

Heating Temperature Control function (C.T.R.)

When the heating water temperature selector is positioned in the 

sector containing the white indicators, the C.T.R. self-control function 

is activated. According to the temperature set on the room thermostat 

and the time taken to reach this value, the boiler automatically varies 

the heating water temperature, reducing operating time and enabling 

increased comfort and energy savings.

Содержание START AQUA 24 BI

Страница 1: ...START AQUA 24 BI EN INSTALLER AND USER MANUAL HU TELEP T I S FELHASZN L I K ZIK NYV...

Страница 2: ...rticle 7 2 and Annex III of directive 92 42 EEC Electromagnetic compatibility directive 2004 108 EC Low voltage directive 2006 95 EC Directive 2009 125 EC Ecodesign for energy using appliances Directi...

Страница 3: ...ntact the Technical Assistance service or a professionally qualified technician immediately Do not touch the appliance when barefoot or with any wet parts of the body Do not clean the boiler without h...

Страница 4: ...e boiler is run on combustible gas of a specific weight great er than that of air the electrical parts must be positioned at a minimum height of 500 mm from the ground The boiler cannot be installed o...

Страница 5: ...ormer with a secondary circuit connected to the earth The earth wire must be approximately 2 cm longer than the other wires You must use a general trip switch to disconnect the line in compliance with...

Страница 6: ...to within this range the boiler sup plies domestic hot water and heating In the event of a heating re quest the boiler turns on The digital display indicates the heating water temperature In the event...

Страница 7: ...of the panel and then turn it forwards Unscrew the tapping point screw upstream of the gas valve by ap proximately two turns and connect a pressure gauge Open a hot water tap to the maximum setting t...

Страница 8: ...ntil the pressure is between 1 and 1 5 bar Turn the function selector back to the required setting If there are frequent drops in pressure please request support from the Technical Assistance Service...

Страница 9: ...Using a fork wrench CH10 turn the adjustment nut for maximum output to obtain the value specified in Table 1 TABLE 1 NATURAL GAS G20 LIQUID GAS BUTANE G30 PROPANE G31 Maximum DHW pressure downstream...

Страница 10: ...e combustion chamber and tighten the screws securing it to the gas manifold Position the cable gland with the spark plug wires on the air cham ber Reconnect the spark plug wire Refit the combustion ch...

Страница 11: ...doors and windows to ventilate the room close the gas shut off device contact the Technical Assistance service or a professionally qualified technician immediately Do not touch the boiler when barefoo...

Страница 12: ...uest The boiler operates until the controlled temperatures are reached or the heat demand is met after which it returns to standby status F Temporary shutdown During temporary absences weekends short...

Страница 13: ...rvice Fault A04 The digital display shows the fault code together with the symbol Check the pressure shown on the water gauge if the pressure is less than 0 3 bar set the function selector to OFF and...

Страница 14: ...110 90 NOx S A at maximum minimum less than p p m 150 130 200 130 220 130 NOx Class 2 Maximum heating operating pressure bar 3 Minimum pressure for standard operation bar 0 45 Maximum temperature allo...

Страница 15: ...Seasonal space heating energy efficiency s 78 For boiler space heaters and boiler combination heaters useful heat output For boiler space heaters and boiler combination heaters useful efficiency At ra...

Страница 16: ...vagy szakk pzett szem lyzetet Tilos a kaz nt meg rinteni mez tl b s nedves testr szekkel Tilos b rmilyen folyamatot v gezni miel tt a kaz nt lev lasztja az elektromos t ph l zatr l a berendez s f kap...

Страница 17: ...a a kaz nt a leveg nehezebb fajs ly ghet g zzal l tja el akkor az elektromos r szeket a padl t l 500 mm n l maga sabb helyre telep tse A kaz nokat k lt rre nem telep theti mert nem k lt ri m k d sre t...

Страница 18: ...del s eredete nem is mert akkor haszn ljon szigetel transzform tort m sodlagos f ldel ssel A f ldel s p r cm rel legyen hosszabb a t bbin l K telez A CEI EN 60335 1 szabv nyoknak megfelel t bbp lus me...

Страница 19: ...at Helyezze a kaz nt elektromos ell t s al Nyissa ki a g zcsapot hogy lehet v tegye az zemanyag ram l s t Szab lyozza a k rnyezeti termoszt tot a k v nt h m rs kletre 20 C Forgassa el a m k d skiv las...

Страница 20: ...k s ekkor v g rehajthatja a k vetkez folyamatokat Ellen rizheti az ell t g z nyom s t Ellen rizheti az g st Az ell t g z nyom s ellen rz se helyezze a berendez s f kapcsol j t kikapcsolt ll sba Hajtsa...

Страница 21: ...03 rendelleness gek ll tsa a m k d s kiv laszt t ll sba OFF v rjon 5 6 m sod percet s ll tsa vissza a k v nt helyzetbe Ha a felenged si pr b lkoz sok nem aktiv lj k jra a kaz nt akkor k rje a M szaki...

Страница 22: ...y s a minim lis s maxi m lis elektromos f t s szab lyoz s t a megadott sorrendben v gezze kiz r lag a M szaki gyf lszolg lat val Helyezze a berendez s f kapcsol j t kikapcsolt ll sba Szerelje le az tk...

Страница 23: ...ment se n lk l a k vetkez k t m d egyik t v lassza a ll tsa a m k d skiv laszt t ll sba kikapcsolt felenge dett b sz ntesse meg az ell t fesz lts get A tar z funkci automatikusan befejez dik a minim l...

Страница 24: ...t s Tiszt tsa meg a k penyt a vez rl panelt a f nyezett s a m anyag r szeket szappanos v zt l nedves ruh val Makacs szennyez d s eset n 50 os v z s denatur lt szesz keve r kkel vagy speci lis term kk...

Страница 25: ...zagot rez Ebben az esetben szell ztesse ki a helyis get nyissa ki az ajt kat s az abla kokat z rja el az zemanyag elz r berendez st azonnal t j koztassa a M szaki gyf lszolg latot vagy szakk pzett sze...

Страница 26: ...ktromos s az zemanya ell t st akt van hagyva a kaz n a k vetkez rendszerekkel v dett Fagy sg tl Amikor a meleg v z h m rs klete 5 C al s llyed s bekapcsolja a keringet t s sz ks g eset n az g fejet mi...

Страница 27: ...t t kikapcsolt OFF ll sba s nyissa meg a felt lt csapot am g 1 s 1 5 bar k zti nyom s rt ket r el Ezt k vet en helyezze a m k d skiv laszt t a k v nt helyzetbe a kaz n 2 perces l gtelen t ciklust v ge...

Страница 28: ...rt ken 6 0 2 5 4 1 1 7 7 0 3 0 6 8 2 8 CO S A maximum minimum rt ken alacsonyabb mint p p m 80 80 240 400 120 90 110 90 NOx S A maximum minimum rt ken alacsonyabb mint p p m 150 130 200 130 220 130 N...

Страница 29: ...y Pn vleges 24 kW Szezon lis helyis gf t si hat sfok s 78 Helyis gf t kaz nok s kombin lt kaz nok eset ben hasznos h teljes tm ny Helyis gf t kaz nok s kombin lt kaz nok eset ben hat sfok M rt h telje...

Страница 30: ...iler at low temperature Caldeira de baxa temperatura Chaudi re basse temp rature 12 13 17 EN Boiler functional elements 1 Filling tap 2 Water pressure switch 3 Discharge valve 4 3 way valve 5 Safety v...

Страница 31: ...n M Heating delivery AC Hot water outlet AF Cold water inlet HU Hidraulikus k r 1 Leereszt csap 2 Biztons gi szelep 3 By pass 4 Kipufog szelep 5 V z nyom skapcsol 6 Keringtet 7 L gtelen t szelep 8 F h...

Страница 32: ...eat adjustment indicates the connection to an external probe Flame Flame failure this icon is visualised together with irregularity code A 01 Irregularity indicates any operating irregularities togeth...

Страница 33: ...isplay and integrated ignition transformer P1 Potentiometer to select off summer winter reset temperature heating P2 Potentiometer to select domestic hot water set point P3 Potentiometer to select tem...

Страница 34: ...OLUME cm3 DATA DAT MODIFICATO DA MODIFIED BY DESCRIZIONE DELLA MODIFICA DISEGNATORE DESIGNER DESCRIZIONE FINITURA MATERIALE RIELLO QUOTE SENZA INDICAZIONE DI TOLLERANZA E RIFER PROCEDURA OPERATIVA RIE...

Страница 35: ...400 450 500 550 600 650 0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 A 6 metre standard modulating pump curves 6 m teres sz riamodul tor keringet g rbe B 7 metre high head modul...

Страница 36: ...START AQUA 24 BI 36 8 7 6 5 3 4 370 50 mm 50 mm 370 mm R M G AC AF...

Страница 37: ...START AQUA 24 BI 37 12 11 10 9 B 13 E A B C D 3 4 1 2 5 3 4 1 2 5 14...

Страница 38: ......

Страница 39: ......

Страница 40: ...Cod 20117085 03 16 Ed 0...

Отзывы: