START AQUA 24 BI

10

-  Disconnect the pressure gauge and refit the pressure tapping point 

screw

  To complete calibration without memorising the values set, either:

 

a) set the function selector to   (OFF-unblock)

 

b) disconnect the power supply

  Calibration is completed automatically, without memorising the 

minimum or maximum values, 15 minutes after activation.

  The function is also terminated automatically in the event of a 

shutdown or permanent block. Again, values are NOT memo-

rised.

NOTE:

 to calibrate only the maximum heating value, remove jumper 

JP2 (to memorise the maximum value) and then exit the function 

without memorising the minimum value by setting the function selec-

tor to OFF or by turning the boiler off at the mains.

  After any intervention on the gas valve adjustment component, 

seal with sealing paint.

4.9 

Converting from one gas type to another

The boiler is supplied to operate with natural gas (G20) or LPG (G30/

G31) according to the specifications on the technical data plate.

However, it may be converted from one type of gas to another by us-

ing the special kits available on request.

-  Natural gas conversion kit

-  LPG conversion kit

  This conversion procedure must only be carried out by the 

Technical Assistance Service or by personnel authorised, also 

once the boiler has been installed.

  For information on assembly, please refer to the instructions 

supplied with the kit.

  After converting the boiler, it must be adjusted again. Follow 

the instructions in the relevant paragraph and apply the new 

identification data plate supplied in the kit.

-  Turn off the power to the boiler and shut off the gas valve

-  Remove the following in sequence: case, air chamber cover and 

combustion chamber cover

-  Disconnect the spark plug wire

-  Unscrew the burner screws

-  Remove the cable gland from the air chamber and remove the 

burner with the spark plug attached

-  Using a box spanner or fork wrench, remove the nozzles and 

washers and replace them with those supplied in the kit

  Use and fit the washers supplied in the kit only, even for mani-

folds without washers.

-   Refit the burner in the combustion chamber and tighten the screws 

securing it to the gas manifold

-  Position the cable gland with the spark plug wires on the air cham-

ber

-  Reconnect the spark plug wire

-  Refit the combustion chamber cover and the air chamber cover

-  Remove the cover to access the jumpers

-  To convert from natural gas to LPG, wire in the jumper at position 

JP3

-  To convert from LPG to natural gas, remove the jumper from posi-

tion JP3

-  Turn the boiler on again and reopen the gas valve

-  Adjust the boiler as explained in the chapter “Adjustments”. This 

must be done exclusively by the Technical Assistance Service.

-  Refit the cover

-  Apply the adhesive gas identification label supplied in the kit (red 

for LPG or yellow for natural gas) to replace the previous version

-  Refit the case.

Adjust the boiler as described in the chapter “Adjustments”, referring 

to the data for LPG.

  The conversion procedure must be carried out exclusively by 

qualified technicians

  On completion of conversion, apply the new ID data plate sup-

plied in the kit.

4.10  Boiler cleaning

Before cleaning, disconnect the electric power supply by switching 

the main system switch to “OFF”.

External cleaning

Clean the casing, the control panel, the painted parts and the plastic 

parts with damp, soapy cloths.

For stubborn stains, dampen the cloth with a 50% water and dena-

tured alcohol mixture, or use specific products.

  Never use fuel and/or sponges soaked in abrasive solutions or 

powder detergents.

Internal cleaning

Before cleaning the inside:

-  Shut off the gas valves 

-  Close the system taps.

4.11  Cleaning the water tank (fig. 14)

After removing the flange it will be possible to inspect and clean insi-

de the water tank and check the condition of the magnesium anode.

-  Turn off the hot water system stopcock and empty the water tank 

through the drainage device (fig. 13)

-  Loosen the nut and extract the anode (

1

)

-  Remove the nuts (

2

) blocking the external flange (

3

) and extract it

-  Clean the inside surfaces and remove all the debris through the 

opening

-  Check the wear conditions of the magnesium anode (

1

), replace 

if necessary

-  Check that the gasket (

4

) is in good condition after extracting it 

from the inside flange (

5

), replace if necessary.

Complete the work of cleaning, re-mount the components working 

the other way round to above description.

Содержание START AQUA 24 BI

Страница 1: ...START AQUA 24 BI EN INSTALLER AND USER MANUAL HU TELEP T I S FELHASZN L I K ZIK NYV...

Страница 2: ...rticle 7 2 and Annex III of directive 92 42 EEC Electromagnetic compatibility directive 2004 108 EC Low voltage directive 2006 95 EC Directive 2009 125 EC Ecodesign for energy using appliances Directi...

Страница 3: ...ntact the Technical Assistance service or a professionally qualified technician immediately Do not touch the appliance when barefoot or with any wet parts of the body Do not clean the boiler without h...

Страница 4: ...e boiler is run on combustible gas of a specific weight great er than that of air the electrical parts must be positioned at a minimum height of 500 mm from the ground The boiler cannot be installed o...

Страница 5: ...ormer with a secondary circuit connected to the earth The earth wire must be approximately 2 cm longer than the other wires You must use a general trip switch to disconnect the line in compliance with...

Страница 6: ...to within this range the boiler sup plies domestic hot water and heating In the event of a heating re quest the boiler turns on The digital display indicates the heating water temperature In the event...

Страница 7: ...of the panel and then turn it forwards Unscrew the tapping point screw upstream of the gas valve by ap proximately two turns and connect a pressure gauge Open a hot water tap to the maximum setting t...

Страница 8: ...ntil the pressure is between 1 and 1 5 bar Turn the function selector back to the required setting If there are frequent drops in pressure please request support from the Technical Assistance Service...

Страница 9: ...Using a fork wrench CH10 turn the adjustment nut for maximum output to obtain the value specified in Table 1 TABLE 1 NATURAL GAS G20 LIQUID GAS BUTANE G30 PROPANE G31 Maximum DHW pressure downstream...

Страница 10: ...e combustion chamber and tighten the screws securing it to the gas manifold Position the cable gland with the spark plug wires on the air cham ber Reconnect the spark plug wire Refit the combustion ch...

Страница 11: ...doors and windows to ventilate the room close the gas shut off device contact the Technical Assistance service or a professionally qualified technician immediately Do not touch the boiler when barefoo...

Страница 12: ...uest The boiler operates until the controlled temperatures are reached or the heat demand is met after which it returns to standby status F Temporary shutdown During temporary absences weekends short...

Страница 13: ...rvice Fault A04 The digital display shows the fault code together with the symbol Check the pressure shown on the water gauge if the pressure is less than 0 3 bar set the function selector to OFF and...

Страница 14: ...110 90 NOx S A at maximum minimum less than p p m 150 130 200 130 220 130 NOx Class 2 Maximum heating operating pressure bar 3 Minimum pressure for standard operation bar 0 45 Maximum temperature allo...

Страница 15: ...Seasonal space heating energy efficiency s 78 For boiler space heaters and boiler combination heaters useful heat output For boiler space heaters and boiler combination heaters useful efficiency At ra...

Страница 16: ...vagy szakk pzett szem lyzetet Tilos a kaz nt meg rinteni mez tl b s nedves testr szekkel Tilos b rmilyen folyamatot v gezni miel tt a kaz nt lev lasztja az elektromos t ph l zatr l a berendez s f kap...

Страница 17: ...a a kaz nt a leveg nehezebb fajs ly ghet g zzal l tja el akkor az elektromos r szeket a padl t l 500 mm n l maga sabb helyre telep tse A kaz nokat k lt rre nem telep theti mert nem k lt ri m k d sre t...

Страница 18: ...del s eredete nem is mert akkor haszn ljon szigetel transzform tort m sodlagos f ldel ssel A f ldel s p r cm rel legyen hosszabb a t bbin l K telez A CEI EN 60335 1 szabv nyoknak megfelel t bbp lus me...

Страница 19: ...at Helyezze a kaz nt elektromos ell t s al Nyissa ki a g zcsapot hogy lehet v tegye az zemanyag ram l s t Szab lyozza a k rnyezeti termoszt tot a k v nt h m rs kletre 20 C Forgassa el a m k d skiv las...

Страница 20: ...k s ekkor v g rehajthatja a k vetkez folyamatokat Ellen rizheti az ell t g z nyom s t Ellen rizheti az g st Az ell t g z nyom s ellen rz se helyezze a berendez s f kapcsol j t kikapcsolt ll sba Hajtsa...

Страница 21: ...03 rendelleness gek ll tsa a m k d s kiv laszt t ll sba OFF v rjon 5 6 m sod percet s ll tsa vissza a k v nt helyzetbe Ha a felenged si pr b lkoz sok nem aktiv lj k jra a kaz nt akkor k rje a M szaki...

Страница 22: ...y s a minim lis s maxi m lis elektromos f t s szab lyoz s t a megadott sorrendben v gezze kiz r lag a M szaki gyf lszolg lat val Helyezze a berendez s f kapcsol j t kikapcsolt ll sba Szerelje le az tk...

Страница 23: ...ment se n lk l a k vetkez k t m d egyik t v lassza a ll tsa a m k d skiv laszt t ll sba kikapcsolt felenge dett b sz ntesse meg az ell t fesz lts get A tar z funkci automatikusan befejez dik a minim l...

Страница 24: ...t s Tiszt tsa meg a k penyt a vez rl panelt a f nyezett s a m anyag r szeket szappanos v zt l nedves ruh val Makacs szennyez d s eset n 50 os v z s denatur lt szesz keve r kkel vagy speci lis term kk...

Страница 25: ...zagot rez Ebben az esetben szell ztesse ki a helyis get nyissa ki az ajt kat s az abla kokat z rja el az zemanyag elz r berendez st azonnal t j koztassa a M szaki gyf lszolg latot vagy szakk pzett sze...

Страница 26: ...ktromos s az zemanya ell t st akt van hagyva a kaz n a k vetkez rendszerekkel v dett Fagy sg tl Amikor a meleg v z h m rs klete 5 C al s llyed s bekapcsolja a keringet t s sz ks g eset n az g fejet mi...

Страница 27: ...t t kikapcsolt OFF ll sba s nyissa meg a felt lt csapot am g 1 s 1 5 bar k zti nyom s rt ket r el Ezt k vet en helyezze a m k d skiv laszt t a k v nt helyzetbe a kaz n 2 perces l gtelen t ciklust v ge...

Страница 28: ...rt ken 6 0 2 5 4 1 1 7 7 0 3 0 6 8 2 8 CO S A maximum minimum rt ken alacsonyabb mint p p m 80 80 240 400 120 90 110 90 NOx S A maximum minimum rt ken alacsonyabb mint p p m 150 130 200 130 220 130 N...

Страница 29: ...y Pn vleges 24 kW Szezon lis helyis gf t si hat sfok s 78 Helyis gf t kaz nok s kombin lt kaz nok eset ben hasznos h teljes tm ny Helyis gf t kaz nok s kombin lt kaz nok eset ben hat sfok M rt h telje...

Страница 30: ...iler at low temperature Caldeira de baxa temperatura Chaudi re basse temp rature 12 13 17 EN Boiler functional elements 1 Filling tap 2 Water pressure switch 3 Discharge valve 4 3 way valve 5 Safety v...

Страница 31: ...n M Heating delivery AC Hot water outlet AF Cold water inlet HU Hidraulikus k r 1 Leereszt csap 2 Biztons gi szelep 3 By pass 4 Kipufog szelep 5 V z nyom skapcsol 6 Keringtet 7 L gtelen t szelep 8 F h...

Страница 32: ...eat adjustment indicates the connection to an external probe Flame Flame failure this icon is visualised together with irregularity code A 01 Irregularity indicates any operating irregularities togeth...

Страница 33: ...isplay and integrated ignition transformer P1 Potentiometer to select off summer winter reset temperature heating P2 Potentiometer to select domestic hot water set point P3 Potentiometer to select tem...

Страница 34: ...OLUME cm3 DATA DAT MODIFICATO DA MODIFIED BY DESCRIZIONE DELLA MODIFICA DISEGNATORE DESIGNER DESCRIZIONE FINITURA MATERIALE RIELLO QUOTE SENZA INDICAZIONE DI TOLLERANZA E RIFER PROCEDURA OPERATIVA RIE...

Страница 35: ...400 450 500 550 600 650 0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 A 6 metre standard modulating pump curves 6 m teres sz riamodul tor keringet g rbe B 7 metre high head modul...

Страница 36: ...START AQUA 24 BI 36 8 7 6 5 3 4 370 50 mm 50 mm 370 mm R M G AC AF...

Страница 37: ...START AQUA 24 BI 37 12 11 10 9 B 13 E A B C D 3 4 1 2 5 3 4 1 2 5 14...

Страница 38: ......

Страница 39: ......

Страница 40: ...Cod 20117085 03 16 Ed 0...

Отзывы: