43
RIELLOTECH CLIMA TOP - CLIMA COMFORT
RIELLOTECH CLIMA TOP - CLIMA COMFORT
Operat-
ing line
User
level Function
Default value
Min
Max
Unit
3881
F
Antifreeze concentration
30
1
100
%
3884
F
Pump capacity
- - -
10
1500
l/h
3886 (**)
F
Pulse count yield
None ¦ With input H1 ¦ With input H3 ¦ With input H31 Module 1 ¦
With input H31 Module 2 ¦ With input H31 Module 3 ¦ With input
H32 Module 1 ¦ With input H32 Module 2 ¦ With input H32 Module 3
¦ With input H33
None
-
-
-
3887 (**)
F
Pulse unit yield
None ¦ kWh ¦ Liter
None
-
-
-
3888 (**)
F
Pulse value yield numer
10
1
1000
-
3889 (**)
F
Pulse value yield denom
10
1
1000
-
3891(**)
F
Flow measurement yield
None ¦ With input H1 ¦ With input H31 Module 1 ¦ With input H31
Module 2 ¦ With input H31 Module 3 ¦ With input H31 Module 1 ¦
With input H31 Module 2 ¦ With input H31 Module 3 ¦ With input
H32 Module 1 ¦ With input H32 Module 2 ¦ With input H32 Module 3
¦ With input H3
None
-
-
-
3896(**)
F
Readj solar flow sensor
0
-20
20
°C
3897(**)
F
Readj solar return sensor
0
-20
20
°C
Solid fuel boiler
4102
F
Locks other heat sources
Off ¦ On
On
-
-
-
4103(**)
F
Charg prio DHW stor tank
Off ¦ On
Off
-
-
-
4110
F
Setpoint min
40
8
120
°C
4114(**)
F
Temp differential min
4
0
40
°C
4130
F
Temp diff on
4
1
40
°C
4131(***)
F
Temp diff off
4
0
40
°C
4133(***)
F
Comparative temp DHW
sensor B3 ¦ DHW sensor B31 ¦ Buff st tank sensor B4 ¦ Buff st tank
sensor B41 ¦ Flow temp setpoint ¦ Setpoin min
Setpoint min
-
-
-
4134(**)
F
Connection DHW stor tank
With B3 ¦ With B31 ¦ With B3 and B31
With B3
-
-
-
4135(**)
F
Boiler temp setp DHW charg
Storage tank temp ¦ Storage tank setpoint ¦ Boiler temp setpoint
min
Storage tank temper-
ature
-
-
-
4136(**)
F
DHW charging with Q3
No ¦ Yes
Yes
-
-
-
4137(**)
F
Connection buffer
With B4 ¦ With B42/B41 ¦ With B4 and B42/B41
With B4
-
-
-
4138(**)
F
Boil temp setp buffer charg
Storage tank temp ¦ Storage tank setpoint ¦ Boiler temp setpoint
min
Storage tank temper-
ature
-
-
-
4140
F
Pump overrun time
20
0
120
min
4141
O
Excess heat discharge
90
60
140
°C
4153(**)
F
Return setpoint min
8
8
95
°C
4154(**)
O
Return setpoint min OEM
8
8
95
°C
4158(**)
F
Flow influence return ctrl
Off ¦ On
Off
-
-
-
4163(**)
O
Actuator running time
120
30
873
s
4164(**)
O
Mixing valve Xp
24
1
100
°C
4165(**)
O
Mixing valve Tn
90
10
873
s
4170
O
Frost prot plant boiler pump
Off ¦ On
Off
-
-
-
4190(**)
F
Residual heat fct dur max
- - -
5
60
min
4192(**)
F
Residual heat fct trigg
Once / Several times
Once
-
-
-
4201(**)
F
Pump speed min
40
0
OL 4202
%
4202(**)
F
Pump speed max
100
OL 4201
100
%
Buffer storage tank
4720
F
Auto generation lock
None ¦ With B4 ¦ With B4 and B42/B41
With B4
-
-
-
4721
O
Auto heat gen lock SD
2
0
20
°C
4722
F
Temp diff buffer/HC
-5
-20
20
°C
4723(**)
O
Temp diff buffer/CC
0
-20
20
°C
4724
O
Min st tank temp heat mode
- - -
- - - / 8
95
°C