36
RIELLOTECH CLIMA TOP - CLIMA COMFORT
RIELLOTECH CLIMA TOP - CLIMA COMFORT
Operat-
ing line
User
level Function
Default value
Min
Max
Unit
900
F
Optg mode changeover
None ¦ Protection ¦ Reduced ¦ Comfort ¦ Automatic
Protection mode
-
-
-
Cooling circuit 1
901(**)
E
Operating mode
Off ¦ Automatic
Automatically
-
-
-
902(**)
E
Comfort setpoint
24,0
15
40
°C
907(**)
E
Release
24h/day ¦ Time progr HC ¦ Time program 5
24h / day
-
-
-
908(**)
I
Flow temp setp at OT 25°C
20
8
35
°C
909(**)
I
Flow temp setp at OT 35°C
16
8
35
°C
912(**)
I
Cooling limit at OT
20
- - - / 8
355
°C
913(**)
F
Lock time at end of heating
24
- - - / 8
100
h
918(**)
F
Summer comp start at OT
26
20
35
°C
919(**)
F
Summer comp end at OT
35
20
35
°C
920(**)
F
Summer comp setp increase
4
- - - / 1
10
°C
923(**)
F
Flow temp setp min OT 25°C
18
8
35
°C
924(**)
F
Flow temp setp min OT 35°C
18
8
35
°C
928(**)
F
Room influence
80
- - - / 1
10
%
932(**)
F
Room temp limitation
0,5
- - - /
0.5
4
°C
937(**)
F
Frost prot plant CC pump
Off ¦ On
Off
-
-
-
938(**)
F
Mixing valve decrease
0
0
20
°C
939(**)
F
Actuator type
2-position ¦ 3-position
3-position
-
-
-
940(**)
F
Switching differential 2-pos
2
0
20
°C
941(**)
F
Actuator running time
120
30
873
s
942(**)
O
Mixing valve Xp
12
1
100
°C
943(**)
O
Mixing valve Tn
90
10
873
s
945(**)
F
Mixing valve in heating mode
Control ¦ Open
Controls
-
-
-
946(**)
F
Lock time dewpoint monitor
60
- - - / 10
600
min
947(**)
F
Flow temp setp incr hygro
10
- - - / 1
10
°C
948(**)
F
Flow setp incr start at r.h.
60
0
100
%
950(**)
I
Flow temp diff dewpoint
2
- - - / 0
10
°C
962(**)
F
With buffer
No ¦ Yes
No
-
-
-
963(**)
F
With prim contr/system pump
No ¦ Yes
No
-
-
-
969(**)
I
Optg mode changeover
None ¦ Off ¦ Automatic
Off
-
-
-
Heating circuit 2
1000
E
Operating mode
Protection ¦ Automatic ¦ Reduced ¦ Comfort
Automatically
-
-
-
1010
E
Comfort setpoint
20,0
OL 1012
OL 1016
°C
1012
E
Reduced setpoint
16
OL 1014
OL 1010
°C
1014
E
Frost protection setpoint
10,0
4
OL 1012
°C
1016
F
Comfort setpoint max
35,0
OL 1010
35
°C
1020
E
Heating curve slope
1,50
0,10
4,00
-
1021
F
Heating curve displacement
0,0
-4,5
4,5
°C
1026
F
Heating curve adaption
Off ¦ On
Off
-
-
-
1030
E
Summer/winter heating limit
18
- - - / 8
30
°C
1032
F
24-hour heating limit
-3
- - - /
-10
10
°C
1033(**)
O
Ext’n 24-hour heating limit
No ¦ Yes
Yes
-
-
-
1040
I
Flow temp setpoint min
8
8
OL 1041
°C
1041
I
Flow temp setpoint max
80
OL 1040
95
°C
1042(**)
F
Flow temp setpoint room stat
65
OL 1040
OL 1041
°C
1044(**)
O
Swi-on ratio room stat
- - -
- - - / 1
99
%