RIELLOTECH CLIMA TOP - CLIMA COMFORT
RIELLOTECH CLIMA TOP - CLIMA COMFORT
Operat-
ing line
User
level Function
Default value
Min
Max
Unit
6215
I
Check no. storage tank
-
0
199999
-
6217
I
Check no. heating circuits
-
0
199999
-
6220
I
Software version
-
0
99,9
-
6222
O
Device hours run
0
0
65535
h
6270(**)
F
Excess heat discharge temp
95
20
350
°C
6271(**)
F
SD excess heat discharge
4
0
50
°C
6272(**)
F
Excess heat discharge sens
None ¦ DHW sensor B31 ¦ Collector sensor B6 ¦ Return sensor B7 ¦
Buffer st tank sensor B4 ¦ Buffer st tank sensor B41 ¦ Flue gas sen-
sor B8 ¦ Common flow temperature sensor B10 ¦ Solid fuel boiler
sensor B22 ¦ Buffer st tank sensor B42 ¦ Common return sensor B73
¦ Cascade return sensor B70 ¦ Swimming pool sensor B13 ¦ Collector
sensor 2 B61 ¦ Solid fuel return sensor B72 ¦ Boiler sensor B2 ¦ DHW
sensor B3.
None
-
-
-
6273(**)
F
Excess heat dischar dur min
0
0
42
min
6345(**)
O
Code commissioning
0
0
99999
-
6346(**)
O
Code engineer
0
0
99999
-
6358(**)
F
Voltage output GX1
5 Volt ¦ 12 Volt
5 Volt
-
-
-
LPB system
6600
I
Device address
1
0
16
-
6601
F
Segment address
0
0
14
-
6604
F
Bus power supply function
Off ¦ Automatically
Automatically
-
-
-
6605
F
Bus power supply state
Off ¦ On
On
-
-
-
6610
O
Display system messages
No ¦ Yes
Yes
-
-
-
6612
O
Alarm delay
- - -
- - - / 2
60
min
6620
F
Action changeover functions
Segment ¦ System
System
-
-
-
6621
F
Summer changeover
Locally¦ Centrally
Local
-
-
-
6623
F
Optg mode changeover
Locally ¦ Centrally
Centrally
-
-
-
6624
F
Manual source lock
Lokal ¦ Segment
Local
-
-
-
6625
F
DHW assignment
Local HCs ¦ All HCs in segment ¦ All HCs in system
All HCs in system
-
-
-
6627 (**)
F
Refrigeration request
Locally¦ Centrally
Local
-
-
-
6630
F
Cascade master
Always ¦ Automatically
Automatically
-
-
-
6631
F
Ext source in Eco mode
Off ¦ On DHW ¦ On
On
-
-
-
6632(**)
F
Note OT limit ext source
No ¦ Yes
No
-
-
-
6640
I
Clock mode
Autonomously ¦ Slave without remote setting ¦ Slave with remote
setting ¦ Master
Autonomously
-
-
-
6650
F
Outside temp source
0
0
239
-
Fault
6710
I
Reset alarm relay
No ¦ Yes
No
-
-
-
6740
F
Flow temp 1 alarm
- - -
- - - / 10
240
min
6741
F
Flow temp 2 alarm
- - -
- - - / 10
240
min
6742(**)
F
Flow temp 3 alarm
- - -
- - - / 10
240
min
6743
F
Boiler temp alarm
- - -
- - - / 10
240
min
6745
F
DHW charging alarm
- - -
- - - / 1
48
h
6746 (**)
F
Flow temp cooling 1 alarm
- - -
- - - / 10
240
min
6800
F
History 1
-
-
-
-
6801
F
Error code 1
-
0
255
-
6802
F
History 2
-
-
-
-
6803
F
Error code 2
-
0
255
-
6804
F
History 3
-
-
-
-