35
RIELLOTECH CLIMA TOP - CLIMA COMFORT
RIELLOTECH CLIMA TOP - CLIMA COMFORT
Operat-
ing line
User
level Function
Default value
Min
Max
Unit
Heating circuit 1
700
E
Operating mode
Protection ¦ Automatic ¦ Reduced ¦ Comfort
Automatically
-
-
-
710
E
Comfort setpoint
20,0
OL 712
OL 716
°C
712
E
Reduced setpoint
16
OL 714
OL 710
°C
714
E
Frost protection setpoint
10,0
4
OL 712
°C
716
F
Comfort setpoint max
35,0
OL 710
35
°C
720
E
Heating curve slope
1,50
0,10
4,00
-
721
F
Heating curve displacement
0,0
-4,5
4,5
°C
726
F
Heating curve adaption
Off ¦ On
Off
-
-
-
730
E
Summer/winter heating limit
18
- - - / 8
30
°C
732
F
24-hour heating limit
-3
- - - /
-10
10
°C
733(**)
O
Ext’n 24-hour heating limit
No ¦ Yes
Yes
-
-
-
740
I
Flow temp setpoint min
8
8
OL 741
°C
741
I
Flow temp setpoint max
80
OL 740
95
°C
742(**)
F
Flow temp setpoint room stat
65
OL 740
OL 741
°C
744(**)
O
Swi-on ratio room stat
- - -
- - - / 1
99
%
750
F
Room influence
20
- - - / 1
100
%
760
F
Room temp limitation
1
- - - /
0.5
4
°C
770
F
Boost heating
3
- - - / 0
20
°C
780
F
Quick setback
Off ¦ Down to reduced setpoint ¦ Down to frost prot setpoint
Down to reduced set
point
-
-
-
790
F
Optimum start control max
0
0
360
min
791
F
Optimum stop control max
0
0
360
min
794(**)
F
Heat up gradient
60
0
600
Min/K
800
F
Reduced setp increase start
- - -
- - - /
-30
10
°C
801
F
Reduced setp increase end
-15
-30
OL 800
°C
810(**)
F
Frost prot plant HC pump
Off ¦ On
On
-
-
-
820
F
Overtemp prot pump circuit
Off ¦ On
On
-
-
-
830
F
Mixing valve boost
5
0
50
°C
832
F
Actuator type
2-position ¦ 3-position
3-position
-
-
-
833
F
Switching differential 2-pos
2
0
20
°C
834
F
Actuator running time
120
30
873
s
835
O
Mixing valve Xp
32
1
100
°C
836
O
Mixing valve Tn
120
10
873
s
850
I
Floor curing function
Off ¦ Functional heating ¦ Curing heating ¦ Functional/curing heat-
ing ¦ Curing/functional heating ¦ Manually
Off
-
-
-
851
I
Floor curing setp manually
25
0
95
°C
856(**)
I
Floor curing day current
0
0
32
-
857(**)
I
Floor curing days completed
0
0
32
-
861
F
Excess heat draw
Off ¦ Heating mode ¦ Always
Always
-
-
-
870
F
With buffer
No ¦ Yes
Yes
-
-
-
872
F
With prim contr/system pump
No ¦ Yes
Yes
-
-
-
880(**)
F
Pump speed reduction
Operating level ¦ Characteristic
Characteristic
-
-
-
882
F
Pump speed min
40
0
OL 883
%
883
F
Pump speed max
100
OL 882
100
%
888(**)
O
Curve readj at 50% speed
33
0
100
%
890(**)
O
Flow setp readj speed ctrl
No ¦ Yes
Yes
-
-
-