56
RIELLOTECH CLIMA TOP - CLIMA COMFORT
RIELLOTECH CLIMA TOP - CLIMA COMFORT
Operat-
ing line
User
level Function
Default value
Min
Max
Unit
7471(**)
F
Function input H21 module 3
None ¦ Optg mode change HCs+DHW ¦ Optg mode changeover
DHW ¦ Optg mode changeover HCs ¦ Optg mode changeover HC1 ¦
Optg mode changeover HC2 ¦ Optg mode changeover HC3 ¦ Het
gen lock ¦ Error/alarm message ¦ Consumer request VK1 ¦ Consumer
request VK2 ¦ Release swi pool source heat ¦ Excess heat discharge
¦ Release swi pool solar ¦ Operating level DHW ¦ Operating level HC1
¦ Operating level HC2 ¦ Operating level HC3 ¦ Room thermostat HC1 ¦
Room thermostat HC2 ¦ Room thermostat HC3 ¦ DHW flow switch ¦
Circ pump thermostat ¦ Pulse count ¦ Dewpoint monitor ¦ Flow
temp setp incr hygro ¦ Boiler return thermostat ¦ Status info suppl
source ¦ Charg prio DHW sol fuel boil ¦ Flow measurement Hz ¦
Consumer request VK1 10V ¦ Consumer request VK2 10V ¦ Pressure
measurement 10V ¦ Rel room humidity 10V ¦ Room temp 10V ¦ Flow
measurement 10V ¦ Temp measurement 10V
-
-
-
-
7472(**)
F
Contact type H21 module 3
NC ¦ NO
NO
-
-
-
7474(**)
F
Input value 1 H21 module 3
0
0
1000
-
7475(**)
F
Funct value 1 H21 module 3
0
-100
500
-
7476(**)
F
Input value 2 H21 module 3
10
0
1000
-
7477(**)
F
Funct value 2 H21 module 3
100
-100
500
-
7478(**)
F
Temp sensor H21 module 3
None ¦ Solar flow sensor B63 ¦ Solar return sensor B64
None
-
-
-
7481(**)
F
Function input H22 module 3
OL 7471
-
-
-
-
7482(**)
F
Contact type H22 module 3
NC ¦ NO
NO
-
-
-
7484(**)
F
Input value 1 H22 module 3
0
0
1000
-
7485(**)
F
Funct value 1 H22 module 3
0
-100
500
-
7486(**)
F
Input value 2 H22 module 3
10
0
1000
-
7487(**)
F
Funct value 2 H22 module 3
100
-100
500
-
7488(**)
F
Temp sensor H22 module 3
None ¦ Solar flow sensor B63 ¦ Solar return sensor B64
None
-
-
-
7491(**)
F
Voltage out GX21 module 3
5 Volt ¦ 12 Volt
5 Volt
-
-
-
7492(**)
I
Funct input EX21 module 3
None ¦ Counter 1st burner stage ¦ Heat gen lock ¦ Error/alarm mes-
sage ¦ Excess heat discharge
-
-
-
-
7493(**)
O
Cont type EX21 module 3
NC ¦ NO
NO
-
-
-
7498(**)
F
Funct output UX21 module 3
None ¦ Boiler pump Q1 ¦ DHW pump Q3 ¦ DHW interm circ pump
Q33 ¦ Heat circuit pump HC1 Q2 ¦ Heat circuit pump HC2 Q6 ¦ Heat
circuit pump HC3 Q20 ¦ Collector pump Q5 ¦ Solar pump ext exch
K9 ¦ Solar pump buffer K8 ¦ Solar pump swi pool K18 ¦ Collector
pump 2 Q16 ¦ Instant WH pump Q34 ¦ Solid fuel boiler pump Q10 ¦
Boiler setpoint ¦ Output request ¦ Heat request ¦ Refrigeration
request ¦ Burner modulation
-
-
-
-
7499(**)
F
Sign logic out UX21 module3
Standard ¦ Inverted
Standard
-
-
-
7500(**)
F
Signal output UX21 module 3
0..10V ¦ PWM
0,,10V
-
-
-
7504(**)
F
Temp val 10V UX21 module3
100
5
130
°C
7505(**)
F
Funct output UX22 module 3
OL 7498
-
-
-
-
7506(**)
F
Sign logic out UX22 module3
Standard ¦ Inverted
Standard
-
-
-
7507(**)
F
Signal output UX22 module 3
0..10V ¦ PWM
0,,10V
-
-
-
7511(**)
F
Temp val 10V UX22 module3
100
5
130
°C
Input / output test
7700
I
Relay test
No test ¦ Everything off ¦ Burner stage T2 ¦ DHW pump Q3 ¦ Heating
circuit pump Q2 ¦ Heating circ mix valve op Y1 ¦ Heat circ mix valve
cl Y2 ¦ Relay output QX1 ¦ Relay output QX21 module 1 ¦ Relay output
QX22 module 1 ¦ Relay output QX23 module 1 ¦ Relay output QX21
module 2 ¦ Relay output QX22 module 2 ¦ Relay output QX23 mod-
ule 2 ¦ Relay output QX21 module 3 ¦ Relay output QX22 module 3 ¦
Relay output QX23 module 3.
No test
-
-
-
7710(***)
I
Output test UX
-
0
100
%
7711(***)
I
Voltage signal UX
0
0
10
Volt