7.3 Drain hole position
8/10/12/14/16 kW
4/6 kW
Drain hole
This drain hole is
covered by rubber
plug. If the smaller
drain hole can not
meet the drainage
requirements, the
bigger drain hole can
be used at the same
time.
Drain hole
NOTE
It's necessary to install an electrical heating belt if water can't drain out in cold weather, even the bigger drain hole has opened.
7.4 Servicing space requirements
7.4.1 In case of stacked installation
1) In case obstacles exist in front of the outlet side.
2) In case obstacles exist in front of the air inlet.
7.4.2
≥500mm
A
≥200mm
2) In case obstacles exist in front of the air inlet.
≥500mm
≥200mm
≥300mm
In case of multiple-row installation (for roof top use, etc)
In case of installing multiple units in lateral connecting per row
≥500mm
≥500mm
B2
A
B1
C
H
Unit
A(mm)
4~6kW
≥1000
8~16kW
≥1500
Unit
A(mm)
B1(mm)
B2(mm)
C(mm)
4~6kW
≥2500
≥1000
≥300
≥600
8~16kW
≥3000
≥1500