110
ENGLISH
Table 9-2
1-phase 4-16kW standard and 3-phase 12-16kW standard
Outdoor Unit
Power Current
Compressor
OFM
System
Voltage (V)
Hz
Min. (V) Max . (V) MCA (A) TOCA (A) MFA (A) MSC (A) RLA (A)
KW
FLA (A)
4kW
220-240
50
198
264
12
18
25
-
11,50
0,10
0,50
6kW
220-240
50
198
264
14
18
25
-
13,50
0,10
0,50
8kW
220-240
50
198
264
16
19
25
-
14,50
0.17
1,50
10kW
220-240
50
198
264
17
19
25
-
15,50
0.17
1,50
12kW
220-240
50
198
264
25
30
35
-
23,50
0,17
1,50
14kW
220-240
50
198
264
26
30
35
-
24,50
0,17
1,50
16kW
220-240
50
198
264
27
30
35
-
25,50
0,17
1,50
12kW 3-PH
380-415
50
342
456
10
14
16
-
9,15
0,17
1,50
14kW 3-PH
380-415
50
342
456
11
14
16
-
10,15
0,17
1,50
16kW 3-PH
380-415
50
342
456
12
14
16
-
11,15
0,17
1,50
NOTE
MCA : Max. Circuit Amps. (A)
TOCA : Total Over-current Amps. (A)
MFA : Max. Fuse Amps. (A)
MSC : Max. Starting Amps. (A)
RLA : In nominal cooling or heating test condition the input Amps of compressor where MAX. Hz can operate Rated Load Amps. (A)
KW : Rated Motor Output
FLA : Full Load Amps. (A)
9.7.5
Remove the switch box cover
1-phase 4-16kW standard and 3-phase 12-16kW standard
Unit
4kW
6kW
8kW
10kW 12kW 14kW 16kW 12kW 3-PH 14kW 3-PH 16kW 3-PH
Maximum overcurrent
protector(MOP)(A)
18
18
19
19
30
30
30
14
14
14
Wiring size(mm
2
)
4.0
4.0
4.0
4.0
6.0
6.0
6.0
2.5
2.5
2.5
UNIT POWER SUPPLY
1-phase
L
N
L N
LPS
FUSE
UNIT POWER SUPPLY
3-phase
LPS
FUSE
L1
N
L2 L3
L3
N
L2
L1
UNIT POWER SUPPLY
3-phase
LPS
FUSE
L1
N
L2 L3
L3
N
L2
L1
UNIT POWER SUPPLY
1-phase
L N
LPS
FUSE
NOTE
The ground fault circuit interrupter m
ust be 1 high-speed type of 30mA(<0.1s). Please use 3-core shielded wire.
The default of backup heater is option 3 (for 9kW backup heater). If 3kW or 6kW backup heater is needed, please ask professional installer to
change the Dip switch of S1 to option 1(for 3kW backup heater) or option 2(for 6kW backup heater), refer to 10.1.1 FUNCTION SETTING.
Stated values are maximum values (see electrical data for exact values).