5.9 Automatic Control (ACS) (24 V AC/DC)
You can connect the RMC400 control-unit to an automatic control-system (ACS). Refer to the
diagram that follows and connect the ACS. Also refer to the product manual of the ACS that is used.
Notes:
•
When the two inputs of the digital control (pin 1 and 3) receive a control signal at the same time,
the control unit will not process them. The electric motor does not move.
•
The external power supply can be 24 V AC/DC.
•
Refer to §3.5 for the technical specifications of the external power supply of connector X6.
Connector X6 of the control-board (A2) can be connected to
automatic control-systems (ACS) that have a “switched ground” or a
“switched positive”.
5.10 OPTIONAL - Manual Control (MC)
You can connect the RMC400 control-unit (without built-in MC) to a manual control (MC) such as
the Ridder MC Module Compact (277950).
•
Remove the jumper from connection 1 and 3 of X8.
•
Connect the manual control (MC). Refer to the diagram that follows.
Refer to the related manual when you connect a different manual control (MC).
Control-board A2
Control-board A2
YES
NO
MC