Rheem RHPL-HM2421JC Скачать руководство пользователя страница 21

21

Profile D – Dry Climate profile
The Dry Climate profile is configured for areas that require little to no additional dehu-
midification.

5.11 CONVENTIONAL 24VAC THERMOSTAT CONTROL WIRING 

The (-)PRL series of heat pumps allow the installer to use conventional 24VAC control
wiring and a conventional thermostat for proper unit operation. 

IMPORTANT: The preferred method of unit installation and operation is by the Comfort
Control

2

System™, which allows access to the fault history of the system. This diagnos-

tic information is not available when the (-)PRL unit is using a conventional thermostat.
Reference section 5.1 Comfort Control

2

System™ Control Wiring. 

Thermostat control wiring requires a minimum of eight (8) wires for proper unit operation: 

R – 24VAC 
C – 24VAC common 
G – Constant Fan 
W1 – First stage electric heat 
W2 – Second stage electric heat 
Y1 – First stage operation 
Y2 – Second stage operation 
B – Heat pump operation 

Optional wiring: 

ODD – On demand humidification 

NOTE: W1 and W2 may be jumpered together to energize all the electric heat when a
call for electric heat is received if warmer supply air temperature is desired. 

NOTE: When using 24VAC thermostat control wiring, the serial communicating control
will ignore any inputs to Data wire 1 and Data wire 2. 

IMPORTANT: Class 2 low voltage control wire should not be run in conduit with power
wiring and must be separated from power wiring, unless Class 1 wire of proper voltage
rating is used. 

Low voltage control wiring should be 18 AWG color-coded (105°C minimum).  For
lengths longer than 100 ft., 16 AWG wire should be used. 

Low voltage control connections are made by extending wires from top of air handler
using wire nuts. 

See wiring diagrams attached to indoor and outdoor sections to be connected 

Do not leave excess field control wiring inside unit, pull excess control wire to outside of
unit and provide strain relief for field wiring on inside of cabinet at point wiring penetrates
cabinet. 

Make sure, after installation, separation of control wiring and power wiring has been
maintained.

5.12 USING THE ON-BOARD LED TO DETERMINE BLOWER CFM 

The CFM LED indicates blower output by flashing one (1) flash for every 100 CFM of air-
flow. The LED will pause 1/10 second between each flash. 

5.13 COOLING AIRFLOW SETTINGS 

FIGURE 18

DIP SWITCH SETTING FOR COOLING AIRFLOW

 

8

 

6.2 Serial Communications Control  

 

The (-)HPL series air handler control, figure X.X, has the following features: 

 

 

An automotive-style ATC blade fuse for transformer protection (3 amp). 

 

An on-board LED to indicate blower CFM. 

 

An RJ-11 port for use with a diagnostic tool. 

 

Inputs for field installed supply and return air temperature sensors (available in kit RXHT-

A01) 

 

DIP switches for airflow adjustments 

 

IMPORTANT:

  A diagnostic tool can be used to display any air handler diagnostic codes.  

However, no system changes are permitted.  Any system changes MUST be done via the DIP 

switches. 

 

Installation Verification 

 

24V AC power on R&C must be present at the control for the air handler to operate 

 

Line voltage must be present at the control for indoor blower operation. 

 

The control wires must be connected to a conventional 24VAC thermostat for proper 

operation. 

 

6.3 Using the On-Board LED to Determine Blower CFM 

 

The (-)HPL interface board LED indicates blower output by flashing one (1) second for every 

100 CFM of airflow.  The LED will pause 1/10 second between each flash.  After the blower 

CFM has been displayed, the LED will illuminate dimly for 10 seconds before repeating the 

sequence. (See Table 1.) 

 

 

6.4 Cooling Airflow Settings 

 

 

 

Figure X – DIP switch setting for cooling airflow 

 

CONVENTIONAL THERMOST

A

T WIRING

On Delay

Air Handler

Delay Duration

(second)

% Rated Airflow

Off Delay (seconds)

RHPL-HM2421

150

88

60

RHPL-HM3621

150

88

60

RHPL-HM4824

150

88

60

RHPL-HM6024

150

88

60

Содержание RHPL-HM2421JC

Страница 1: ...as an aid to qualified licensed service personnel for proper installation adjustment and operation of this unit Read these instructions thoroughly before attempting installation or operation Failure...

Страница 2: ...Board LED to Determine Blower CFM 21 5 13 Cooling Airflow Settings 21 5 14 Cooling Airflow Adjustments with Single Stage Condensing Units 22 5 15 Heating Airflow Adjustment 22 5 16 Airflow Adjustment...

Страница 3: ...ts such as dirt dust fumes and odors into the home causing property damage Fumes and odors from toxic volatile or flammable chemicals as well as automobile exhaust and carbon monoxide CO can be drawn...

Страница 4: ...d below are those chemicals and substances commonly associated with similar equipment in our industry and other manufacturers Glass Wool Fiberglass Insulation Carbon Monoxide CO Formaldehyde Benzene M...

Страница 5: ...e control module CAUTION SEE SECTION 13 2 INDOOR COIL DRAIN PAN DRAIN LINE In compliance with recognized codes it is recommended that an auxiliary drain pan be installed under all evaporator coils or...

Страница 6: ...ion of toxic fumes and odors including carbon monoxide from migrating into the living space If air moving equipment or ductwork is located in spaces containing fuel burning appliances such as water he...

Страница 7: ...stall the unit in such a way as to allow necessary access to the coil filter rack and blower control compartment Install the unit in a level position to ensure proper condensate drainage Make sure uni...

Страница 8: ...IR OPENING UPFLOW UNIT SHOWN UNIT MAY BE INSTALLED UPFLOW DOWNFLOW HORIZONTAL RIGHT OR LEFT AIR SUPPLY Model Return Air Opening Return Air Opening Cabinet Size Width Inches Depth Length Inches 21 193...

Страница 9: ...for Combustible Floor Base RXHB XX Units with electric heating kW equal to or less than the values listed in the table do not require a combustible floor base Vertical units require clearance on at le...

Страница 10: ...ctory shipped for vertical upflow and horizontal left application If return air is to be ducted install duct flush with floor Use fireproof resilient gasket 1 8 to 1 4 in thick between duct unit and f...

Страница 11: ...lug Tighten lug as tight as possible while holding circuit breaker Check wires and make sure each wire is secure and none are loose Repeat for left wire bundle in left top circuit breaker lug Replace...

Страница 12: ...ason we recommend the fol lowing for all air handler applications but special attention should be paid to those installed in unconditioned spaces Duct sizing and airflow are critical and based on the...

Страница 13: ...lso be accomplished by attaching ground wire s to ground lug s provided in the unit wiring compartment Ground lug s are located close to wire entrance on left side of unit upflow Lug s may be moved to...

Страница 14: ...9 44 RXBH 1724 10J Single 208 240 1 60 5 4 7 2 26 0 30 0 4 9 40 45 39 44 Single 208 240 1 60 10 8 14 4 51 9 60 0 4 9 80 90 72 82 RXBH 1724A15J MULTI CKT 1 208 240 1 60 3 6 4 8 17 3 20 0 4 9 30 35 28 3...

Страница 15: ...onnections to the 24VAC thermostat wires If any connections are made to the G W1 W2 Y1 Y2 B or ODD wires the Comfort Control2 control will assume the control is being used with a tra ditional thermost...

Страница 16: ...bias dip switches should be on 24V AC power on R C must be present at the control for the air handler to operate reference Figure 9 Line voltage must be present at the control for indoor blower opera...

Страница 17: ...erial communications the airflow can only be adjusted usin the serial communicating thermostat or a service tool To adjust the airflow go to the airflow adjustment menu and select the desired adjustme...

Страница 18: ...sing ODD do NOT use any of the alternate profiles Only use the factory default profile Use of the alternate profiles with ODD will decrease energy efficiency with no gain in comfort Profile A Factory...

Страница 19: ...ler Y1 E W1 TypicalTwo StageThermostat PRL Heat Pump Outdoor Unit Y2 C R B Y2 Field Installed Line Voltage WIRING INFORMATION Factory Standard ODD R Y1 Y2 G W2 R Y1 C L D Y Y BL BL R BR W R PR DHM L F...

Страница 20: ...Y R C Y W BL Humidistat G W1 Y2 G BK W BK BL G Y BR R Y BL FIGURE 16 TYPICAL SINGLE STAGE THERMOSTAT SINGLE STAGE STRAIGHT COOLING WITH ELECTRIC HEAT Y2 AIR FLOW G W2 C R HPL Air Handler Single Stage...

Страница 21: ...d control wiring inside unit pull excess control wire to outside of unit and provide strain relief for field wiring on inside of cabinet at point wiring penetrates cabinet Make sure after installation...

Страница 22: ...IRFLOW The HPL series of air handlers are factory configured to for proper airflow The cooling airflow CAF is fixed and the DIP switch settings have no effect on airflow The factory setti is Cooling A...

Страница 23: ...ield adjusted Electric Heat Airflow Thermostat Input 2 ton 3 ton 4 ton 5 ton W1 or W2 800 CFM 1200 CFM 1600 CFM 1800 CFM 6 8 Cooling Mode Dehumidification CONVENTIONAL THERMOSTAT WIRING RHPL HM2421JC...

Страница 24: ...to increase latent capacity The HPL air handler is programmed to provide maximum efficiency and optimum humidity removal When high humidity is detected the air handler reduces cooling airflow defined...

Страница 25: ...ata is obsolete If system will not operate order new memory card to update system information 68 ECM No Signal The ECM motor is not communicating to the air handler control board Make sure the ECM mot...

Страница 26: ...MPORTANT Flanges around blower opening for attaching supply duct must be up out of blower discharge even if not used so they do not restrict airflow from blower IMPORTANT If an elbow is included in th...

Страница 27: ...tside of coil box 7 2 CONDENSATE DRAIN TUBING Consult local codes or ordinances for specific requirements IMPORTANT When making drain fitting connections to the drain pan use a thin layer of Teflon pa...

Страница 28: ...Installed If a remote filter is installed it should be sized for a maximum of 300 feet min air veloci ty for the CFM required IMPORTANT Do not operate system without a filter A filter is required to p...

Страница 29: ...7 0 8 0 9 1 0 550 575 600 600 625 625 625 600 575 550 455 540 620 695 760 825 885 940 985 1030 40 55 70 85 105 120 135 150 170 185 775 775 775 800 800 825 825 825 825 825 540 615 685 750 810 870 925...

Страница 30: ...c resistance heat is BTUH Heating Watts x 3 412 Where 1 kW 1000 Watts 3 412 Btuh Watt 11 3 CALCULATING AIRFLOW CFM The formula for calculating airflow using temperature rise and heating BTUH for units...

Страница 31: ...n been provided under the unit with separate drain Units installed above a finished ceiling Is condensate line properly sized run trapped pitched and tested Is ductwork correctly sized run taped and i...

Страница 32: ...it would become necessary to clean the blower motor and wheel If it becomes necessary to remove the blower assembly from the unit see instruc tions on removal and disassembly of motor blower and heate...

Страница 33: ...aced as they were check wiring diagram if necessary Tighten supply power wiring securely to terminals lugs Make sure wiring is within cabinet and will not interfere with access door Make sure proper s...

Страница 34: ...the motor has locking tabs It has been proven that by applying excessive force to the A C cable half of the connector it is possible to force the connector in backwards It will not seat and click prop...

Страница 35: ...t is necessary to order by part number and include with the order the complete model number and serial number from the unit data plate See parts list for unit component part numbers 15 0 ACCESSORIES K...

Страница 36: ...ERNAL FILTER RACK RXHF B21 B24 B 1 50 A Model Cabinet Size Filter Size Part Number A B 21 20 x 20 RXHF B21 20 40 20 77 24 25 x 20 RXHF B24 25 00 21 04 Accommodate 1 filter Auxiliary Horizontal Overflo...

Страница 37: ...37 FIGURE 29 AIR HANDLER EQUIPPED WITH Serial Communication WIRING DIAGRAM...

Страница 38: ...38...

Страница 39: ...39...

Страница 40: ...40 CM 0411...

Отзывы: