TM081 Rheem 834 Series Hydroelectric CFGWH Service Instructions
REV: AA Issued: 22/02/17
This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed uncontrolled.
31
Fault Finding Chart 1.2
Is flame sensor clean
and free from cracks?
Firmly connect flame sensor
lead to flame sensor.
NO
YES
NO
Is flame sensor
correctly adjusted?
YES
Correctly adjust flame sensor.
Refer to ‘Checking & Adjusting
the Flame Sensor’ in the
‘Component Adjustment
Procedures &
Checks’ section.
NO
1.2
Does main burner
ignite?
Is flame sensor lead
firmly connected to
flame sensor?
Clean flame sensor or replace
pilot assembly. (flame sensor is
not available as a spare part).
Is flame sensor rod
touching a metal
component?
YES
NO
NO
Does pilot light during
ignition period?
YES
NO
Is 1.1 ~ 2.1 VDC
present at SV1 during
ignition period?
(TEST 8)
Replace ignition module.
NO
Is pilot feed pipe, pilot
injector or pilot assy
dirty or blocked?
YES
Replace gas valve assembly.
Clean or replace pilot feed pipe
or pilot assembly (pilot injector is
not available as a spare part).
YES
NO
SV1 is pilot
valve
Is pilot flame
satisfactory?
YES
NO
Pilot flame should extend past
flame rod by approx 5 mm and
flame rod should glow red.
Is pilot injector correct
size for gas type?
Replace pilot injector with one of
the correct size.
YES
NO
Is 1.1 ~ 2.1 VDC
present at SV2 when
pilot is alight?
(TEST 9)
NO
SV2 is main burner
safety valve
Replace ignition module
NO
Fault rectified.
Replace temperature controller
and reinstall original ignition
module.
Does red LED 4 flash
fault indication
persist?
YES
YES
Is 1.1 ~ 2.1 VDC
present at SV3 when
pilot is alight?
(TEST 10)
YES
Replace temperature controller.
NO
Replace gas valve assembly.
YES
1.3
YES
False flame, ignition failure or
loss of flame (continued)
SV3 is main
burner valve