ECODRIVE03 Auxiliary Bleeder Module BZM01.3
ECODRIVE03 Drive Controllers
The signal is set to "High “
•
if pre-warning signal threshold for maximum bleeder load exceeded
(internally permanently set)
•
or if pre-warning signal threshold is exceeded for maximum bleeder
temperature (internally permanently set).
Further operations up to the shutdown threshold is possible but this
causes the Bb contact to open.
Output set to "low"
•
if error is pending
•
if control voltage failed
Clear error
The clear error input supports the resetting of the unit ’s internal error
memory.
AP5310F1.FH7
0V
ext
Clear error
X2
1
2
3
4
5
6
7
8
10
11
12
ClearError
9
0V
Fig. 6-32:
Input clear error
R1
R3
R2
C1
I
n
Ap5183f1.fh7
Schematics
R1:
10k
R2:
3k3
R3:
10k
C1:
10nF
Fig. 6-33:
Input circuit
Input voltage:
High
Low
min.
16 V
-0.5 V
max.
30 V
3 V
m
h
O
k
3
.
3
1
t
u
o
b
a
e
c
n
a
t
s
i
s
e
r
t
u
p
n
I
Fig. 6-34:
Inputs
Giving a positive edge at input the "Clear error", the entire error memory
is deleted.
Warning message:
Ready:
Connection
clear error:
Input circuit
Clear error:
Inputs
Clear error:
Clear error:
|