Mercury 2 & Intuitive Mercury EPR Stepper Installation

 

Guide

 

 

www.resourcedm.com 

P-44 

Def Terminate 

The defrost will terminate (defrost control relay off) when the temperature of the defrost termination probe 
reaches this value. 
If the "defrost termination" probe is not fitted, defrost termination will occur when: - 
 

The "coil in" probe reaches the set point (If fans are selected as "off during defrost") OR 

 

The "air off" probe reaches the set point (If fans are selected as "on during defrost").  

 If the "coil in" probe is not fitted, the "air off" probe will be used.  

P-45 

Def Min Time 

Minimum time that a defrost will use (Defrost can’t terminate until this time has elapsed. If termination 
temperature is reached during this period, the defrost control relay is turned off, but the controller will not 
continue the defrost cycle until the end of the defrost min period) 

P-46 

Def Max Time 

Time period after defrost minimum that defrosts are allowed to terminate 

P-47 

Drain Down 

A period after defrost max to allow the draining of any surplus water 

P-48 

Recovery Time 

The valve is opened at the start of this period to allow the temperature to recover to the normal operating 
point. This period also inhibits the OT alarm.  
Note that if the air-off temperature is still above the OT alarm setpoint when this period expires, an 
immediate OT alarm occurs; there is 

not

 a further alarm delay. 

P-89 

Pump Down Time 

Time period before the defrost min period to allow for a pump down 

P-86 

Fan Delay mode 

This parameter allows the fans start after a drain-down period to be delayed, either by time (P-49) or 
when the temperature point (P-88) is reached. This parameter uses the same probe strategy as the 
defrost terminate. 

P-49 

Fan Delay 

Time after a drain-down period before the fans start if P-86 is set to time 

P-88 

Fan Delay Temp 

Temperature at which the fans start after a drain-down period when P-86 is set to temperature. 

P-50 

Fans In Defrost 

Allows the user to set the fans on or off in defrost.  

Note

 if the fans are set to on in defrost, they will go off 

for the drain-down period and then follow the P-86 rules. 

P-94 

Defrost Hold 

Turns the defrost hold feature on and off. When switched on, the controller can be held in defrost until a 
remote command from the front end starts the recovery process. 

P-95 

Defrost Skip 

Allows user to enable/disable defrost skip. This feature allows the controller to skip defrosts. If the current 
defrost terminates on temperature then the controller will skip the next scheduled defrost providing the 
previous defrost terminated before the defrost skip time (P-96). Operates only when the controller is set to 
local defrost scheduling.  

P-96 

Defrost Skip Time 

Time factor used in defrost skip. The previous defrost has to terminate before this value expires to allow 
the controller to skip a defrost. 

P-80 

Door alarm delay 

Delay after the door open input is activated before the alarm occurs. 

P-81 

Door Closes Valve 

This parameter is used to close the stepper valve if the door opens. If the door remains open then the 
valve will resume normal operation on the expiry of the door alarm delay (P-80). 

P-82 

Door Stops Fan 

This parameter is used to stop the fans if the door opens. If the door remains open then the fans will 
resume normal operation on the expiry of the door alarm delay (P-80). 

P-60 

Lights Mode 

Allows the user to set the lights mode: - 

 

Always off 

 

Always on 

 

Use a local schedule P-61 to P-74) 

 

Use a remote schedule (Set up in the system front end) 

P-61 

Sun Lights On  

When P-60 is set to Local, Sunday on time 

P-62 

Sun Lights Off  

When P-60 is set to Local, Sunday off time 

P-63 

Mon Lights On  

When P-60 is set to Local, Monday on time 

P-64 

Mon Lights Off  

When P-60 is set to Local, Monday off time 

P-65 

Tue Lights On  

When P-60 is set to Local, Tuesday on time 

P-66 

Tue Lights Off  

When P-60 is set to Local, Tuesday off time 

P-67 

Wed Lights On  

When P-60 is set to Local, Wednesday on time 

P-68 

Wed Lights Off  

When P-60 is set to Local, Wednesday off time 

P-69 

Thu Lights On  

When P-60 is set to Local, Thursday on time 

P-70 

Thu Lights Off  

When P-60 is set to Local, Thursday off time 

P-71 

Fri Lights On  

When P-60 is set to Local, Friday on time 

P-72 

Fri Lights Off  

When P-60 is set to Local, Friday off time 

P-73 

Sat Lights On  

When P-60 is set to Local, Saturday on time 

P-74 

Sat Lights Off  

When P-60 is set to Local, Saturday off time 

P-58 

Broadcast ID 

ID of Plant Controller being used to broadcast Suction Pressure 
The Broadcast ID is derived from the Rotary Switch positions set on the Plant controller which is providing 
the remote suction pressure. 

Note:

 No two Plant controllers on a local area network can have the same rotary switches positions set. 

This will have adverse affects on control. 

P-59 

Refrigerant 

Type of refrigerant gas used in the system. See: 

Refrigerant Table

 above 

P-75 

Pressure Units 

Absolute or Gauge 

P-76 

Evap Offset 

Offset to allow for pressure drop over distance  

P-84 

Glide 

Allows the calculated temperature to be offset by subtracting the value at (P-34) 

P-91 

Trans Span 

Total range of the transducer 

P-99 

Trans Offset 

Value below zero 

dFLt 

Restore default values 

Restores all of the parameters to their default values 

Содержание PR0712-EPR

Страница 1: ...52 EPR PR0762 EPR UK OFFICE Resource Data Management Ltd 80 Johnstone Avenue Hillington Industrial Estate Glasgow Scotland G52 4NZ UK 44 0 141 810 2828 sales resourcedm com US OFFICE Resource Data Man...

Страница 2: ...set up method 9 rtc Real time clock 9 type Set view controller type 9 PArA Set view parameters This can be achieved at the network front end 9 Unit Set view temperature unit and Probe type 9 Display...

Страница 3: ...tion Guide www resourcedm com Remote Commands 21 Specification 22 Power requirements 22 General 22 Valve Output 22 Relay Specification 22 Inputs 23 Switched Resistor Example Wiring 23 Installation 23...

Страница 4: ...cury 6 5 Stepper EPR valve controller integral display PR0752 EPR Intuitive Mercury 6 5 Stepper EPR valve controller remote display PR0762 EPR Intuitive Mercury 6 5 Stepper EPR valve controller integr...

Страница 5: ...e Humidity Inputs PR0018 PHI Wireless Mesh Interface for single Mercury PR0730 The Intuitive Mercury Controller is supplied as standard with an internal RS232 network card this allows connection to an...

Страница 6: ...o the chosen configuration See Input Output tables for further details on connections IP Network Card PR0770 Rotary Address Switches Network Collision LED Network Activity LED Network Expansion Port T...

Страница 7: ...tputs Ordering Information When ordering a Mercury Intuitive controller the following ordering scheme can be used to purchase the desired hardware configuration This ensures the controller ships with...

Страница 8: ...hm switched resistors For NTC10K probes use 2k7 Ohm switched resistors For NTC10K 2 probes use 2k2 Ohm switched resistors The resistors used must have a tolerance of 1 or better and the resistor must...

Страница 9: ...arameter list below to find what parameter number corresponds to which actual parameter Pressing the Enter button will show the current value of the selected parameter Press Up or Down to modify the v...

Страница 10: ...ontrol Probe type 0 Use Air on Probe 1 Use Log Probe 1 0 0 P 90 Resistor Case Off 0 Disabled 1 Enabled 0 0 P 92 Fans temperature mode 0 Off 1 Temperature 2 Over temperature 3 Temp OT 1 0 0 P 93 Fans O...

Страница 11: ...s Valve 0 No 1 Yes No No P 82 Door Stops Fan 0 No 1 Yes No No P 60 Lights Mode 0 Local 1 Remote 2 Man Off 3 Man On Local Local P 61 Sun Lights On 00 00 to 23 59 00 01 hh mm 08 00 08 00 P 62 Sun Lights...

Страница 12: ...off when A pre determined temperature is reached P93 When an over temperature alarm is present When either P93 is reached or an OT alarm is present P 93 Fans Off Temperature Temperature for the above...

Страница 13: ...t of motor Care should be taken when setting this parameter as too high a setting could damage the valve motor Valve Manufacturers specification must be followed Has no effect if Valve Type 0 1 2 or 3...

Страница 14: ...t terminates on temperature then the controller will skip the next scheduled defrost providing the previous defrost terminated before the defrost skip time P 96 Operates only when the controller is se...

Страница 15: ...147 Sporlan other CDS 9 16 17 6386 6800 200 215 See Appendix 3 Step Speed also Valve Wiring Manufacturer Model Wiring Colours Connection Description See Stepper Output Carel E3 V Yellow M1B White M1A...

Страница 16: ...rcury Switch user document PR0018 PHI for further details Remote pressure Direct from a Plant Pack Controller Using IP Module P 17 set to Rem1 Rem2 or Rem3 depending on which input the suction transdu...

Страница 17: ...Module or an Intuitive Internal RS485 network card to the controller will govern which set up screens are made available Both modules support the Genus protocol only Display Option 485t 485 Network Ty...

Страница 18: ...You can now set the address using the table below Display Option IP 1 IP Address byte 1 IP 2 IP Address byte 2 IP 3 IP Address byte 3 IP 4 IP Address byte 4 nL Network Mask Length gt 1 Gateway Addres...

Страница 19: ...On I 15 Monitor Probe 49 to 60 56 2 to 140 0 1 Deg I 16 Remote Evaporator Temp 49 to 60 56 2 to 140 0 1 Deg I 17 MOP 0 Off 1 On I 19 Divide Input 0 to 100 1 0 I 20 Remote Pressure 3 4 to 108 0 0 1 Ba...

Страница 20: ...is Case Off then the controller will change to the Normal state Selecting this option will exit the setup menu automatically The display will show CASE OFF An alarm is generated fixed delay of 1 minut...

Страница 21: ...minutes Relay 4 mode Trim Heater Setpoint Command 20O C 34O F Is added to or subtracted from the setpoint Case Off Command 5 0 Sets the controller to Case Off Restores the controller from Case Off to...

Страница 22: ...ng ventilation There is no requirement for forced cooling ventilation Class 2 Insulation No protective Earth is required and none should be fitted No protective Earth is required and none should be fi...

Страница 23: ...C type probes Input type PT1000 or NTC2K or NTC2K25 or NTC10K selectable Comms RS232 with flow control Switched Resistor Example Wiring Installation Panel Cut out and Clearances Mercury Mk2 Flush moun...

Страница 24: ...the controller Each clip has a mounting hole to provide an alternative fixing mechanism to DIN mounting Cleaning Do not wet the controller when cleaning Clean the front by wiping with slightly damped...

Страница 25: ...Speed Set Hz 500 and above 500 86 to 90 90 251 to 333 333 81 to 85 85 201 to 250 250 76 to 80 80 167 to 200 200 71 to 75 75 144 to 166 166 66 to 70 70 126 to 143 143 61 to 65 65 112 to 125 125 56 to...

Отзывы: