Revision 1.2a
Page 11 of 25
Warning
Please Note
The specifications of the product detailed on this
Set-Up Guide may change without notice. RDM
Ltd. shall not be liable for errors or for incidental
or consequential damages, directly and indirectly,
in connection with the furnishing, performance or
misuse of this product or document.
Ensure that all power is
switched off before
installing or maintaining
this product
Mercury 2 & Intuitive Mercury EPR Stepper Installation
Guide
www.resourcedm.com
Number Parameter
Range
o
C (
o
F )
Step
Units
Default LT
o
C (
o
F )
Default HT
o
C (
o
F )
Type
3&4
Type
5&6
P-25
Log Alarm Delay
00:00 to 99:00
01:00
mm:ss 20:00
20:00
P-26
Log UT Alarm
-49 to 60 (-56.2 to 140)
0.1
Deg
-35 (-31)
-1 (30.2)
P-27
Log OT Alarm
-49 to 60 (-56.2 to 140)
0.1
Deg
-12 (10.4)
6 (42.8)
P-28
Monitor OT Alarm
-49 to 60 (-56.2 to 140)
0.1
Deg
20 (68)
20 (68)
P-40
Defrost Mode
0 (Local), 1 (Remote), 2 (External)
Local
Local
P-41
Defrost Start
00:00 to 23:59
00:01 hh:mm 01:00
01:00
P-42
Defrosts per Day
0 to 8
1
6
6
P-43
No Defrost Time
0 to 25
1
hours
12
12
P-44
Def Terminate Temp.
-42 to 30 (-43.6 to 86)
0.1
Deg
14 (57.2)
10 (50)
P-45
Def Min Time
00:00 to 99:00
01:00
mm:ss 05:00
05:00
P-46
Def Max Time
00:00 to 99:00
01:00
mm:ss 24:00
24:00
P-47
Drain Down
00:00 to 24:00
00:15
mm:ss 01:30
01:30
P-48
Recovery Time
00:00 to 99:00
01:00
mm:ss 30:00
30:00
P-89
Pump Down Time
00:00 to 99:00
01:00
mm:ss 00:00
00:00
P-86
Fan Delay mode
0 = Time, 1 = Temp
1
0
0
P-49
Fan Delay Time (Cabinets)
00:00 to 99:00
01:00
mm:ss 00:00
00:00
Fan Delay Time (Coldroom) 00:00 to 99:00
01:00
mm:ss 03:00
03:00
P-88
Fan Delay Temp
-42 to 30 (-43.6 to 86)
0.1
Deg
-20 (-4)
0.0 (32)
P-50
Fans In Defrost
0 (Off), 1 (On)
On
On
P-94
Defrost Hold
0 (Off), 1 (On)
Off
Off
P-95
Defrost Skip
0 (Off), 1 (On)
Off
Off
P-96
Defrost Skip Time
00:00 to 99:00
01:00
mm:ss 12:00
12:00
P-38
Stepper in Defrost
0 = Closed, 1 = Open
1
0
0
P-80
Door Alarm Delay
00:00 to 99:00
01:00
mm:ss 20:00
20:00
P-81
Door Closes Valve
0 (No), 1 (Yes)
No
No
P-82
Door Stops Fan
0 (No), 1 (Yes)
No
No
P-60
Lights Mode
0 (Local), 1 (Remote), 2 (Man Off),
3 (Man On)
Local
Local
P-61
Sun Lights On
00:00 to 23:59
00:01 hh:mm 08:00
08:00
P-62
Sun Lights Off
00:00 to 23:59
00:01 hh:mm 20:00
20:00
P-63
Mon Lights On
00:00 to 23:59
00:01 hh:mm 08:00
08:00
P-64
Mon Lights Off
00:00 to 23:59
00:01 hh:mm 20:00
20:00
P-65
Tue Lights On
00:00 to 23:59
00:01 hh:mm 08:00
08:00
P-66
Tue Lights Off
00:00 to 23:59
00:01 hh:mm 20:00
20:00
P-67
Wed Lights On
00:00 to 23:59
00:01 hh:mm 08:00
08:00
P-68
Wed Lights Off
00:00 to 23:59
00:01 hh:mm 20:00
20:00
P-69
Thu Lights On
00:00 to 23:59
00:01 hh:mm 08:00
08:00
P-70
Thu Lights Off
00:00 to 23:59
00:01 hh:mm 20:00
20:00
P-71
Fri Lights On
00:00 to 23:59
00:01 hh:mm
08:00
08:00
P-72
Fri Lights Off
00:00 to 23:59
00:01 hh:mm
20:00
20:00
P-73
Sat Lights On
00:00 to 23:59
00:01 hh:mm
08:00
08:00
P-74
Sat Lights Off
00:00 to 23:59
00:01 hh:mm
20:00
20:00
P-58
Broadcast ID
0 to 999
1
-
0
0
P-59
Refrigerant
See Refrigerant Table Below
1
-
0
0
P-75
Pressure Units
0 = Absolute 1 = Gauge
1
-
0
0
P-76
Evap Offset
0.0 to 1.0
0.1
-
0.0
0.0
P-84
Glide
0.0 to 5.0
0.1
Deg
0.0
0.0
P-91
Trans Span
-3.4 to 180.0
0.1
Bar
13.8
13.8
P-99
Trans Offset
-3.4 to 180.0
0.1
Bar
0.0
0.0
dFLt
Restore defaults
* Parameters P-06, P-31, P-32, P-33 and P-
35 only have an effect if “Other” is selected when configuring parameter P-30
* Transducer Span and Offset allows for the full range of the transducer to be used.
Span is the full range of the transducer
Offset is the value below zero.
Example:
Danfoss AKS 33 with range: -1 bar to 12 bar
Span would be 190 (13 bar)
Offset would be -15 (-1 bar)
Refrigerant Table
0 = None. 1 = R12. 2 = R13. 3 = R13B1. 4 = R22. 5 = R23. 6 = R32. 7 = R114. 8 = R134A. 9 = R142B. 10 = R227. 11 = R401.
12 = R401A. 13 = R401B. 14 = R402. 15 = R402A. 16 = R402B. 17 = R404A. 18 = R407A. 19 = R407B. 20 = R407C. 21 = R500