Mercury 2 & Intuitive Mercury EPR Stepper Installation
Guide
www.resourcedm.com
Remote Commands
The following commands can be used by a Data Builder program: -
Command
Value to send
Description
Conditions
Defrost Command
1
Initiates a defrost cycle
Defrost mode: remote
Defrost Command
3
Terminates the defrost
Defrost mode: remote
Defrost hold: On
Defrost min state complete
Trim Command
0 to 100%
Sets the trim level to this value (Trim period is 5
minutes)
Relay 4 mode: Trim Heater
Setpoint Command
±20
O
C (±34
O
F)
Is added to or subtracted from the setpoint
Case Off Command
5
0
Sets the controller to Case Off
Restores the controller from Case Off to Normal
Haccp Command
0
1
2
HACCP LED OFF
HACCP LED On
HACCP LED Flashes
Button Command
0
1
2
Buttons backlights Off
Buttons backlights On
Buttons Backlights Flash
EEV Command
2
1
Shuts the EPR valve
Restores the valve to normal operation
Divider Command
0 to 100%
Sets the maximum valve opening to this percentage.
Use an “Analogue Out” block configured to the
controller name and in the value field type in the
command you require. Use a “Setting block” as
the input to the “Analogue Out” block to send the
Value.
See Example on the right, which sets the Trim
Heater on BY10-1 at 40%