Fan Delay after Defrost 

 

The fans will come back on when: - 

The fan delay time has elapsed if the 

“fan delay mode” is set to time 

Or   

If the fan delay mode is set to 

“temp”, the fans will come on when the defrost termination probe reaches the fan delay set point, 

or on the time parameter, whichever occurs first. 

 
If the 

“defrost termination” probe is not fitted, the fans will come on when: - 

 
 

The 

“coil in” probe reaches the control set point (If fans are selected as “off during defrost”) 

Or 

The 

“air off” probe reaches the control set point (If fans are selected as “on during defrost”)   

 

Network Configuration 

 
The final section to setup is the network address. In all instances, this must be done before the controller is plugged into the site network. 
The controllers have an auto-initialise function, which will automatically log the device onto the site network. If the wrong address has 
been entered onto the network, you will have to reset the controller address by setting the address to 00-0, and then re-enter the correct 
address. (You may have to deregister the wrong address from the home system as well). 
 
When logging a Mercury or Intuitive Mercury with an RS232 interface onto a network you must first connect the controller to a 
communications module, this is either a 485 Legacy, RDM Wireless Mesh system, IP Futura or Mercury Switch. When using an Intuitive 
Mercury controller, the controller has to have the correct network card fitted (see “compatible network interfaces”). For connection to a 
Mercury Switch (Hub) or an external network interface, the standard fitment RS232 network card is utilized. 

 
RS485 Legacy module / Intuitive Internal RS485 Network card 

 
Connecting an RS485 legacy Module or an Intuitive Internal RS485 network card to the controller will govern which set up screens are 
made available. 

Both modules support the “Genus” protocol only. 

 

Display 

Option 

485t 

485 Network Type 

485A 

485 Address/Name 

gAdd  

Show underlying network address assigned to controller 

rLog  

Re-log the controller back onto the network 

CLrA  

Clear the address/name from the controller 

ESC 

Exit network menu. 

N.B.

 this option 

must

 be selected to save any changes made in this menu 

 
The 

485t 

option shows a value representing the network type. The possible values are: 

 

Value 

Network Type 

Genus compatible (all versions) 

RDM Wireless Mesh System (Wireless Mesh) 

 
The 

485A

 option shows a value representing either the name of the controller in a Genus compatible or Wireless Mesh network.  

 
Wireless Mesh Communication Module 

 
RDM Wireless Mesh System, please refer to the RDM Wireless Mesh Communication Module user guide, which can be obtained from 
the RDM website, for information regarding connecting a controller to a Wireless Mesh network. 
The value shown in 485A is of the form 

05-6

. This means the controller would try to log onto a Genus compatible or RDM Wireless Mesh 

network using the name ‘RC05-6’. 
 
The 

gAdd

 option displays (in hexadecimal format) the underlying network address assigned to the controller when it was logged onto the 

network. 
 
The 

rLog

 

option allows the controller to be logged back onto the network with its current name. The ‘rLog’ message will flash for 

confirmation. Press the Enter button to execute the command, Up or Down buttons to cancel. 

 

 
 

Fast Network Address Reset 

The 

ClrA

 

option will clear out the network address and name in the controller. The ‘ClrA’ message will flash for confirmation. Press the 

Enter button to execute the command, Up or Down buttons to cancel. 
 
To enter this mode, hold the Enter, Up and Down buttons together for approximately 3 seconds until the message 

ClrA

 appears on the 

display.

 ClrA

 is the first option in the menu consisting of the following options: 

 

 
 
 
 

Display   Option 

ClrA 

Clear the address/name from the controller 

ESC 

Exit Setup mode 

Содержание PR0712-EPR

Страница 1: ...52 EPR PR0762 EPR UK OFFICE Resource Data Management Ltd 80 Johnstone Avenue Hillington Industrial Estate Glasgow Scotland G52 4NZ UK 44 0 141 810 2828 sales resourcedm com US OFFICE Resource Data Man...

Страница 2: ...set up method 9 rtc Real time clock 9 type Set view controller type 9 PArA Set view parameters This can be achieved at the network front end 9 Unit Set view temperature unit and Probe type 9 Display...

Страница 3: ...tion Guide www resourcedm com Remote Commands 21 Specification 22 Power requirements 22 General 22 Valve Output 22 Relay Specification 22 Inputs 23 Switched Resistor Example Wiring 23 Installation 23...

Страница 4: ...cury 6 5 Stepper EPR valve controller integral display PR0752 EPR Intuitive Mercury 6 5 Stepper EPR valve controller remote display PR0762 EPR Intuitive Mercury 6 5 Stepper EPR valve controller integr...

Страница 5: ...e Humidity Inputs PR0018 PHI Wireless Mesh Interface for single Mercury PR0730 The Intuitive Mercury Controller is supplied as standard with an internal RS232 network card this allows connection to an...

Страница 6: ...o the chosen configuration See Input Output tables for further details on connections IP Network Card PR0770 Rotary Address Switches Network Collision LED Network Activity LED Network Expansion Port T...

Страница 7: ...tputs Ordering Information When ordering a Mercury Intuitive controller the following ordering scheme can be used to purchase the desired hardware configuration This ensures the controller ships with...

Страница 8: ...hm switched resistors For NTC10K probes use 2k7 Ohm switched resistors For NTC10K 2 probes use 2k2 Ohm switched resistors The resistors used must have a tolerance of 1 or better and the resistor must...

Страница 9: ...arameter list below to find what parameter number corresponds to which actual parameter Pressing the Enter button will show the current value of the selected parameter Press Up or Down to modify the v...

Страница 10: ...ontrol Probe type 0 Use Air on Probe 1 Use Log Probe 1 0 0 P 90 Resistor Case Off 0 Disabled 1 Enabled 0 0 P 92 Fans temperature mode 0 Off 1 Temperature 2 Over temperature 3 Temp OT 1 0 0 P 93 Fans O...

Страница 11: ...s Valve 0 No 1 Yes No No P 82 Door Stops Fan 0 No 1 Yes No No P 60 Lights Mode 0 Local 1 Remote 2 Man Off 3 Man On Local Local P 61 Sun Lights On 00 00 to 23 59 00 01 hh mm 08 00 08 00 P 62 Sun Lights...

Страница 12: ...off when A pre determined temperature is reached P93 When an over temperature alarm is present When either P93 is reached or an OT alarm is present P 93 Fans Off Temperature Temperature for the above...

Страница 13: ...t of motor Care should be taken when setting this parameter as too high a setting could damage the valve motor Valve Manufacturers specification must be followed Has no effect if Valve Type 0 1 2 or 3...

Страница 14: ...t terminates on temperature then the controller will skip the next scheduled defrost providing the previous defrost terminated before the defrost skip time P 96 Operates only when the controller is se...

Страница 15: ...147 Sporlan other CDS 9 16 17 6386 6800 200 215 See Appendix 3 Step Speed also Valve Wiring Manufacturer Model Wiring Colours Connection Description See Stepper Output Carel E3 V Yellow M1B White M1A...

Страница 16: ...rcury Switch user document PR0018 PHI for further details Remote pressure Direct from a Plant Pack Controller Using IP Module P 17 set to Rem1 Rem2 or Rem3 depending on which input the suction transdu...

Страница 17: ...Module or an Intuitive Internal RS485 network card to the controller will govern which set up screens are made available Both modules support the Genus protocol only Display Option 485t 485 Network Ty...

Страница 18: ...You can now set the address using the table below Display Option IP 1 IP Address byte 1 IP 2 IP Address byte 2 IP 3 IP Address byte 3 IP 4 IP Address byte 4 nL Network Mask Length gt 1 Gateway Addres...

Страница 19: ...On I 15 Monitor Probe 49 to 60 56 2 to 140 0 1 Deg I 16 Remote Evaporator Temp 49 to 60 56 2 to 140 0 1 Deg I 17 MOP 0 Off 1 On I 19 Divide Input 0 to 100 1 0 I 20 Remote Pressure 3 4 to 108 0 0 1 Ba...

Страница 20: ...is Case Off then the controller will change to the Normal state Selecting this option will exit the setup menu automatically The display will show CASE OFF An alarm is generated fixed delay of 1 minut...

Страница 21: ...minutes Relay 4 mode Trim Heater Setpoint Command 20O C 34O F Is added to or subtracted from the setpoint Case Off Command 5 0 Sets the controller to Case Off Restores the controller from Case Off to...

Страница 22: ...ng ventilation There is no requirement for forced cooling ventilation Class 2 Insulation No protective Earth is required and none should be fitted No protective Earth is required and none should be fi...

Страница 23: ...C type probes Input type PT1000 or NTC2K or NTC2K25 or NTC10K selectable Comms RS232 with flow control Switched Resistor Example Wiring Installation Panel Cut out and Clearances Mercury Mk2 Flush moun...

Страница 24: ...the controller Each clip has a mounting hole to provide an alternative fixing mechanism to DIN mounting Cleaning Do not wet the controller when cleaning Clean the front by wiping with slightly damped...

Страница 25: ...Speed Set Hz 500 and above 500 86 to 90 90 251 to 333 333 81 to 85 85 201 to 250 250 76 to 80 80 167 to 200 200 71 to 75 75 144 to 166 166 66 to 70 70 126 to 143 143 61 to 65 65 112 to 125 125 56 to...

Отзывы: