Revision 1.2a 

Page 10 of 25 

 

 

Warning 

 
 
 
 
 
 

Please Note 

The specifications of the product detailed on this 
Set-Up  Guide  may  change  without  notice.  RDM 
Ltd. shall not be liable for errors or for incidental 
or consequential damages, directly and indirectly, 
in connection with the furnishing, performance or 
misuse of this product or document.

 

Ensure that all power is 
switched off before   
installing or maintaining 
this product 

 

Mercury 2 & Intuitive Mercury EPR Stepper Installation

 

Guide

 

 

www.resourcedm.com 

 

Display 

From the function menu scroll to and select diSP. 
Press enter and one of the following values will be shown: - 
0. Controller display will show the whole number and tenths value of a temperature reading. (Default) 
1. Controller display will show temperatures as a whole number. 

 
 

Parameter Tables 

 
Not all parameters apply to all controller types, for example P-83 is Fan Control which only applies to coldroom types 5 & 6, this 
parameter will not appear if the controller is set up as a type 3 or 4 case types. In the following table, the type columns on the right hand 
side will be greyed out if that parameter does not apply to that controller type.  
 

Number  Parameter 

Range  

o

C    (  

o

F  ) 

 

Step 

Units 

Default LT 

o

C ( 

o

F ) 

Default HT 

o

C  ( 

o

F ) 

 Type 

3&4 

 Type 

5&6 

P-01 

Cut-in Temp. 

-42 to 30  (-43.6 to 86) 

0.1 

Deg 

-20  (-4) 

0.0  (32) 

 

 

P-02 

Diff. 

0 to 10   (0 to 18) 

0.1 

Deg 

2  (3.6) 

1.5  (2.7) 

 

 

P-03 

Control Weight 

0 to 100 

50 

50 

 

 

P-04 

Display Weight 

0 to 100 

50 

50 

 

 

P-09 

Response On 

1 to 30 

 

10 

10 

 

 

P-10 

Response Off 

1 to 30 

 

10 

10 

 

 

P-51 

EEV Minimum Opening 

0 - 100% 

10 

10 

 

 

P-56 

EEV Start Opening 

0 - 100% 

10 

10 

 

 

P-55 

Average Valve Opening 

0 - 100% 

100 

100 

 

 

P-57 

EEV Divide Value 

0 - 100% 

 

50 

50 

 

 

P-12 

Relay 3 Mode 

0 = Suction Line, 1 = Defrost Valve 

 

 

 

P-85 

Key-switch Mode 

0 = Case, 1 = Fans only, 2 = toggle, key 
off  

 

 

 

P-87 

Control Probe type 

0 = Use Air on Probe,  
1 = Use Log Probe 

 

 

 

P-90 

Resistor Case Off  

0 (Disabled),1(Enabled) 

 

 

 

 

P-92 

Fans temperature mode 

0 = Off, 1 = Temperature, 
2 = Over-temperature, 3 = Temp/OT 

 

 

 

P-93 

Fans Off Temperature 

-42 to 30  (-43.6 to 86) 

0.1 

Deg 

-10 (14) 

8 (46.4) 

 

 

P-83 

Fan Control 

0 = Off, 1 = Run, 2 = Pulse 

 

 

 

P-78 

Fan Pulse On 

00:00 to 99:00 

01:00 

mm:ss  05:00 

05:00 

 

 

P-79 

Fan Pulse Off 

00:00 to 99:00 

01:00 

mm:ss  30:00 

30:00 

 

 

P-15 

Probe 5 Select 

0 = Defrost, 1 = Monitor 

 

 

 

P-16 

Relay 2 Mode 

0 = Lights, 1 = Alarm 

 

 

 

P-17 

Evap. Select 

0 = Local, 1 = Rem1, 2 = Rem2, 
3 = Rem3, 4 = IoBrd 

 

 

 

P-97 

Control Fail Valve Level  

0 to 100% 

0.1 

 

 

P-29 

Probe 1 Resistor Function  

0 = Plant fault, 1 = External defrost 

 

 

 

P-18 

Service Interval time 

0 to128 

KHrs 

60 

60 

 

 

P-19 

Switch Resistors 

0 (Off), 1 (On) 

 

 

 

 

P-98 

Lights Case Off 

0 (Off), 1 (On), 2 (Unused) 

 

 

 

 

P-30 

Valve Type 

0=Carel, 1=Sporlan1, 2=Sporlan2 
3=Alco, 4=Other* 

--- 

 

 

P-31 

Step Max 

0 to 6800 See: Valve type 

--- 

480 

480 

 

 

P-32 

Step Close 

0 to 6800 See: Valve type 

--- 

500 

500 

 

 

P-33 

Step Speed 

0 to 6800 See: Valve type 

Hz 

50 

50 

 

 

P-34 

mA Peak 

0  to 500 See: Valve Type 

mA 

450 

450 

 

 

P-35 

Half Step 

0 (Off),1 (On) See: Valve Type 

--- 

 

 

P-36 

mA Hold Current 

0 to 500 

 

 

 

P-37 

Shut Speed 

0 to 6800 

Hz 

50 

50 

 

 

P-06 

Shut Enable 

0 (Off), 1 (On) 

 

 

 

P-07 

Shut Time 

00:00 to 99:00 

01:00 

mm:ss  04:00 

04:00 

 

 

P-05 

Overdrive Time 

1 to 25 

hours 

 

 

P-77 

Man Stop Valve/Fans 

0 (Off),1 (On) 

 

 

 

P-39 

Stepper In Case Off 

0 (Off),1 (On) 

 

 

 

P-20 

Alarm Delay 

00:00 to 99:00  

01:00 

mm:ss  20:00 

20:00 

 

 

P-21 

UT Alarm 

-49 to 60  (-56.2 to 140) 

0.1 

Deg 

-30  (-22) 

-2  (28.4) 

 

 

P-22 

OT Alarm 

-49 to 60  (-56.2 to 140) 

0.1 

Deg 

-15  (5) 

5  (41) 

 

 

P-23 

Log Probe Type 

0 (Off), 1 (Logging), 2 (Logging/Alarm) 

 

 

Off 

Off 

 

 

P-24 

Slug Log Probe 

0 (Off), 1 (On) 

 

 

Off 

Off 

 

 

Содержание PR0712-EPR

Страница 1: ...52 EPR PR0762 EPR UK OFFICE Resource Data Management Ltd 80 Johnstone Avenue Hillington Industrial Estate Glasgow Scotland G52 4NZ UK 44 0 141 810 2828 sales resourcedm com US OFFICE Resource Data Man...

Страница 2: ...set up method 9 rtc Real time clock 9 type Set view controller type 9 PArA Set view parameters This can be achieved at the network front end 9 Unit Set view temperature unit and Probe type 9 Display...

Страница 3: ...tion Guide www resourcedm com Remote Commands 21 Specification 22 Power requirements 22 General 22 Valve Output 22 Relay Specification 22 Inputs 23 Switched Resistor Example Wiring 23 Installation 23...

Страница 4: ...cury 6 5 Stepper EPR valve controller integral display PR0752 EPR Intuitive Mercury 6 5 Stepper EPR valve controller remote display PR0762 EPR Intuitive Mercury 6 5 Stepper EPR valve controller integr...

Страница 5: ...e Humidity Inputs PR0018 PHI Wireless Mesh Interface for single Mercury PR0730 The Intuitive Mercury Controller is supplied as standard with an internal RS232 network card this allows connection to an...

Страница 6: ...o the chosen configuration See Input Output tables for further details on connections IP Network Card PR0770 Rotary Address Switches Network Collision LED Network Activity LED Network Expansion Port T...

Страница 7: ...tputs Ordering Information When ordering a Mercury Intuitive controller the following ordering scheme can be used to purchase the desired hardware configuration This ensures the controller ships with...

Страница 8: ...hm switched resistors For NTC10K probes use 2k7 Ohm switched resistors For NTC10K 2 probes use 2k2 Ohm switched resistors The resistors used must have a tolerance of 1 or better and the resistor must...

Страница 9: ...arameter list below to find what parameter number corresponds to which actual parameter Pressing the Enter button will show the current value of the selected parameter Press Up or Down to modify the v...

Страница 10: ...ontrol Probe type 0 Use Air on Probe 1 Use Log Probe 1 0 0 P 90 Resistor Case Off 0 Disabled 1 Enabled 0 0 P 92 Fans temperature mode 0 Off 1 Temperature 2 Over temperature 3 Temp OT 1 0 0 P 93 Fans O...

Страница 11: ...s Valve 0 No 1 Yes No No P 82 Door Stops Fan 0 No 1 Yes No No P 60 Lights Mode 0 Local 1 Remote 2 Man Off 3 Man On Local Local P 61 Sun Lights On 00 00 to 23 59 00 01 hh mm 08 00 08 00 P 62 Sun Lights...

Страница 12: ...off when A pre determined temperature is reached P93 When an over temperature alarm is present When either P93 is reached or an OT alarm is present P 93 Fans Off Temperature Temperature for the above...

Страница 13: ...t of motor Care should be taken when setting this parameter as too high a setting could damage the valve motor Valve Manufacturers specification must be followed Has no effect if Valve Type 0 1 2 or 3...

Страница 14: ...t terminates on temperature then the controller will skip the next scheduled defrost providing the previous defrost terminated before the defrost skip time P 96 Operates only when the controller is se...

Страница 15: ...147 Sporlan other CDS 9 16 17 6386 6800 200 215 See Appendix 3 Step Speed also Valve Wiring Manufacturer Model Wiring Colours Connection Description See Stepper Output Carel E3 V Yellow M1B White M1A...

Страница 16: ...rcury Switch user document PR0018 PHI for further details Remote pressure Direct from a Plant Pack Controller Using IP Module P 17 set to Rem1 Rem2 or Rem3 depending on which input the suction transdu...

Страница 17: ...Module or an Intuitive Internal RS485 network card to the controller will govern which set up screens are made available Both modules support the Genus protocol only Display Option 485t 485 Network Ty...

Страница 18: ...You can now set the address using the table below Display Option IP 1 IP Address byte 1 IP 2 IP Address byte 2 IP 3 IP Address byte 3 IP 4 IP Address byte 4 nL Network Mask Length gt 1 Gateway Addres...

Страница 19: ...On I 15 Monitor Probe 49 to 60 56 2 to 140 0 1 Deg I 16 Remote Evaporator Temp 49 to 60 56 2 to 140 0 1 Deg I 17 MOP 0 Off 1 On I 19 Divide Input 0 to 100 1 0 I 20 Remote Pressure 3 4 to 108 0 0 1 Ba...

Страница 20: ...is Case Off then the controller will change to the Normal state Selecting this option will exit the setup menu automatically The display will show CASE OFF An alarm is generated fixed delay of 1 minut...

Страница 21: ...minutes Relay 4 mode Trim Heater Setpoint Command 20O C 34O F Is added to or subtracted from the setpoint Case Off Command 5 0 Sets the controller to Case Off Restores the controller from Case Off to...

Страница 22: ...ng ventilation There is no requirement for forced cooling ventilation Class 2 Insulation No protective Earth is required and none should be fitted No protective Earth is required and none should be fi...

Страница 23: ...C type probes Input type PT1000 or NTC2K or NTC2K25 or NTC10K selectable Comms RS232 with flow control Switched Resistor Example Wiring Installation Panel Cut out and Clearances Mercury Mk2 Flush moun...

Страница 24: ...the controller Each clip has a mounting hole to provide an alternative fixing mechanism to DIN mounting Cleaning Do not wet the controller when cleaning Clean the front by wiping with slightly damped...

Страница 25: ...Speed Set Hz 500 and above 500 86 to 90 90 251 to 333 333 81 to 85 85 201 to 250 250 76 to 80 80 167 to 200 200 71 to 75 75 144 to 166 166 66 to 70 70 126 to 143 143 61 to 65 65 112 to 125 125 56 to...