DeltaSol

®

 

B Pro

© RESOL 04026 deltasol_b_pro.mon.pmd

Page 16/24

S1

S4

S2

S3

R1

R2

Channel 

Factory setting 

Change to 

Remark 

S1 

Sensor temperature S1 

------------------- 

Collector temperature 

S2 

Sensor temperature S2 

------------------- 

Lower store temperature 

S3 

Sensor temperature S3 

------------------- 

Solid fuel boiler temperature 

S4 

Sensor temperature S4 

------------------- 

Upper/middle store temperature 

H1 

Hours of operation relay 1 

------------------- 

Control value 

H2 

Hours of operation relay 2 

------------------- 

Control value 

FN 

1 1  FN1 = 2 separated 

T-circuits 

DO/1 

 

Switch-on temperature difference solar pump 

DF/1 

 

Switch-off temperature difference solar pump 

SX/1 

60 

 

Maximum store temperature limitaion 

CL/1 

140 

 

Collector temperature limitation 

CX/1 

120 

 

Maximum collector temperature 

CN/1 

10 

 

Minimum temperature limitation is deactivated 

OC/1 

 

System cooling activated 

DO/2 

6  

Switch-on temperature difference for solid fuel boiler charge 

pump 

DF/2 

4  

Switch-off temperature difference for solid fuel boiler charge 

pump 

SX/2 

60 

 

Maximum store temperature limitation 

CL/2 

140 

 

Solid fuel boiler emergency shut down temperature 

CX/2 

120 ------------ 

Switch-on temperature for system cooling has no influence, as 

the system cooling is deactivated (OC/2 = 0)  

CN/2 

10 

60 

60 °C Minimum temperature to avoid condensation of flue gas

OC/2 

System cooling is deactivated 

MM 

 

Manual mode/MM 4 = automatic operation 

PG/VN 

 

 

Program number/version number 

 

The controller compares both temperature differences
between collector sensor S1 and store sensor S2 as well as
between solid hot fuel boiler S3 and store sensor S4. The
warmth of the collector is given to the store, if the switch-
on temperature difference (DO/1) is exceeded. The pump
R1 remains activated until the switch-off temperature

difference (DF/1) is underrun. The solid hot fuel boiler is
activated by control of the pump R2, if the 2nd switch-on
temperature difference (DO/2) as well as the additionnally
preadjusted minimum temperature (CN/2) are exceeded (in
order to avoid flue gas condensation). The store is only loa-
ded up until the adjusted maximum store temperature (SX1/
2).

Necessary adjustment: Kanal FN=1

6.3 Solar system with 1 collector, 1 store and after-

heating by solid hot fuel boiler:

Содержание DeltaSol B Pro

Страница 1: ...DeltaSol B Pro www resol de RESOL DeltaSol B Pro Mounting Connection Handling Fault localization Examples Thanks for buying a RESOL Read this manual carefully to get the best perfomance from this unit...

Страница 2: ...Comissioning 11 5 Tips for fault localization 11 6 Examples 12 6 1 1 collector 1 store with heating reverse raising14 6 2 System with store charge by solid hot fuel boiler with heating reverse raising...

Страница 3: ...roller configuration as well as a comprehensive visualisation of the system status The following standard basic systems are provided 1 2 separated T circuits 2 2 stores with valve charge logic 3 East...

Страница 4: ...DeltaS eltaS eltaS eltaS eltaSol ol ol ol ol B Pro full kit 115 420 20 incl 3 temperatur sensors Pt1000 2 x FKP6 1 x FRP6 Please find detailed connection schemes for the shown systems in chapter 6 1 c...

Страница 5: ...und hole pitch 130 mm afterwards put the lower dowel 4 Fasten the housing at the underground 1 Installation Warning Switch off power supply before opening the housing 1 2 Electrical wiring The power s...

Страница 6: ...ameter cpl with fastening collar FK 21 or FR 21 Ensure good thermal contact of the sensor with the pipe work by cleaning the contact area and by applying heat conduction paste between sensor and pipe...

Страница 7: ...H2 Hours of Oparation Relay 2 FN FuNction 1 2 separated T circuits 2 2 stores 1 collector 2 stores 3 East West system 2 collectors 1 store 4 1 store with thermostat function 1 collector 1 store with...

Страница 8: ...This indication value can not be reset 3 2 3 Function FN FN 1 2 separate T circuits FN 2 2 stores 1 collector 2 stores FN 3 East west 2 collectors 1 store FN 4 1 store and thermostat function 1 collec...

Страница 9: ...ng for switch on temperature difference is 6 K and the switch off temperature difference is set to 4 K Please note Switch on temperature difference DO must be at least 1 K higher than the switch off t...

Страница 10: ...er days and ensures a thermal relief for the collectors and the heating medium The maximum collector temperature is set to 120 C by RESOL but it can be changed within the adjustment range of 100 C 190...

Страница 11: ...mperature is again underrun In doing so the store temperature can increase subordinated active store safety shutdown but only up to 95 C safety shutdown of the store If the store temperature is higher...

Страница 12: ...er heating TO TF the thermostat function is used as use of surplus energy If the 2nd relay output is activated in the display is shown 3 2 11Thermostat function TO TF System 4 FN 4 After heating use o...

Страница 13: ...uated at the base isolation plate and can be replaced by opening the cover of the housing spare fuse is enclosed in one of the accessory bags 2 Sensor faults If there is a malfunction due to a sensor...

Страница 14: ...ore temperature S4 sensor temperature S4 Heating circuit reverse temperature H1 Hours of operation relay 1 Control value H2 Hours of operation relay 2 Control value FN 1 1 FN1 2 separated T circuits D...

Страница 15: ...Solid fuel boiler emergency shut down temperature CX 1 120 switch on temperature for system cooling has no influence as the system cooling is deactivated OC 1 0 CN 1 10 60 60 C minimum temperature to...

Страница 16: ...ion CL 2 140 Solid fuel boiler emergency shut down temperature CX 2 120 Switch on temperature for system cooling has no influence as the system cooling is deactivated OC 2 0 CN 2 10 60 60 C Minimum te...

Страница 17: ...re temperature limitation of existing store CL 2 140 This adjustment channel has ne relevance in this case CX 2 120 Switch on temperature for system cooling has no influence as the system cooling is d...

Страница 18: ...emperature S2 Store temperature 1 S3 Sensor temperature S3 Store temperature 2 S4 Sensor temperature S4 Measuring sensor only without operational function H1 Hours of operation relay 1 Control value F...

Страница 19: ...llector temperature limitation CX 1 120 Maximum collector temperature CN 1 10 Minimum temperature limitation is deactivated OC 1 1 System cooling is activated DO 2 6 Switch on temperature difference s...

Страница 20: ...relay 1 Control value H2 Hours of operation relay 2 Control value FN 1 3 FN3 Solar system with East West collectors DO 1 6 Switch on temperature difference collector 1 DF 1 4 Switch off temperature di...

Страница 21: ...ry adjustment Channel FN 4 Channel Factory setting Change to Remark S1 Sensor temperature S1 Collector temperature S2 Sensor temperature S2 Lower store temperature TT Sensor temperature S3 Upper store...

Страница 22: ...ent Channel FN 4 Channel Factory setting Change to Remark S1 Sonsor temperature S1 Collector temperature S2 Sonsor temperature S2 Lower store temperature TT Sonsor temperature S3 Upper store temperatu...

Страница 23: ...DeltaSol B Pro RESOL 04026 deltasol_b_pro mon pmd Page 23 24...

Страница 24: ...eltaSol B Pro RESOL 04026 deltasol_b_pro mon pmd Page 24 24 Your wholesaler Notes Design and specifications are subject to change without notice Illustrations may differ slightly from production model...

Отзывы: