3.2.4
∆∆∆∆∆
T-regulation (
DO 1/DO 2, DF 1/DF 2
)
The controller controls the temperatures measured by four
sensors S1, S2, S3 and S4 and compares the resulting
temperature difference with the preadjusted switch-on-
temperature difference
∆
Ton (DO). The controller switches
ON, if the measured temperature difference DT is higher
than or identical to the preadjusted set value in channel DO.
In the display is shown
and the operating control lamp
flashes green. If the adjusted switch-off-temperature-
difference
∆
Toff (DF) is underrun, the controller switches-
OFF. The factory setting for switch-on temperature
difference is 6 K and the switch-off temperature difference
is set to 4 K.
Please note:
Switch-on temperature difference DO must
be at least 1 K higher than the switch-off temperature
difference DF.
DO
:urn-on temperature
difference
adjustable values 1,5 ... 10 K
factory setting 6.0
DF
:Turn-off temperature
difference
adjustable values 1 ... 9,5 K
factory setting 4.0 K
3.2.5 Maximum store temperature (
SX 1/SX 2
)
If the adjusted maximum temperature is exceeded, a furt-
her loading of the store is stopped so that a damaging
overheating can be avoided. If the maximum store
temperature is exceeded, in the display is shown
and
(flashing), the operating control lamp flashes red.
SX 1
: Maximum store temperature circuit 1
SX 2
: Maximum store temperature circuit 2
adjustable values 2 ... 95 °C
factory setting 60 °C