6. Examples
6.1 Solar system with 1 collector and 1 store with
heating reverse raising
The controller measures the temperature difference between
collector sensor S1 and store sensor S2. As soon as this
difference is higher or identical to the adjusted value for
switch-on temperature difference (DO/1), the pump (R1) is
activated and the store is loaded until the switch-off
temperature difference (DF/1) or the maximum store
temperature (SX/1) is reached. Independently from the so-
lar circuit a
∆
T-reverse raising is simultaneously effected. If
the switch-on temperature difference (DO/2) of the sensors
S3 and S4 is exceeded a 3-way valve is activated for heating
circuit support by relay output R2.
Channel
Factory setting
Change to
Remark
S1
sensor temperature S1
-------------------
Collector temperature
S2
sensor temperature S2
-------------------
Lower store temperature
S3
sensor temperature S3
-------------------
Upper store temperature
S4
sensor temperature S4
-------------------
Heating circuit reverse temperature
H1
Hours of operation relay 1
-------------------
Control value
H2
Hours of operation relay 2
-------------------
Control value
FN
1 1
FN1 = 2 separated
∆
T circuits
DO/1
6
switch-on temperature difference solar pump
DF/1
4
switch-off temperature difference solar pump
SX/1
60
Maximum store temperature limitation
CL/1
140
Collector
limitation
temperature
CX/1
120
Maximum collector temperature
CN/1
10
Minium temperature limitation is deactivated
OC/1
1
System cooling is on
DO/2
6
switch-on temperature difference for 3-way-valve
reverse lifting
DF/2
4
switch-off temperature difference for 3-way-valve
reverse lifting
SX/2
60
The 3-way-valve is switched off as soon as the adjusted value
is reached in the heating circuit reverse.
CL/2
140
This adjustment channel has no relevance in this case
CX/2
120
switch-on temperature for system cooling has no influence,
as the system cooling is switched off (OC/2=0)
CN/2
10
Minimum temperature limitation for the reverse lifting is
deactivated
OC/2
1
0
system cooling is switched off
MM
4
Manual mode
MM 4 = automatic operation
PG/VN
Program
number/Version