DeltaSol
®
B Pro
© RESOL 04026 deltasol_b_pro.mon.pmd
Page 15/24
6.2 System with store charge by solid hot fuel
boiler with heating reverse raising
The solid hot fuel boiler is added on by control of the pump
R1, if the switch-on temperature difference (DO/1) as well
as the aditionally preadjusted minimum temperature (CN/
1) is exceeded (in order to avoid flue gas condensation).
The store is only loaded up to the adjusted maximum store
Channel
Factory setting
Change to
Remark
S1
sensor temperature S1
-------------------
Measuring value
S2
sensor temperature S2
-------------------
Measuring value
S3
sensor temperature S3
-------------------
Measuring value
S4
sensor temperature S4
-------------------
Measuring value
H1
Hours of operation relay 1
-------------------
Control value
H2
Hours of operation relay 2
-------------------
Control value
FN
1 1
FN1 = 2 separated
∆
T-circuits
DO/1
6
switch-on temperature difference
loading pump for solid fuel boiler
DF/1
4
switch-off temperature difference
loading pump for solid fuel boiler
SX/1
60
Maximum store temperature limitation
CL/1
140
Solid fuel boiler emergency shut down temperature
CX/1
120 ------------
switch-on temperature for system cooling has no influence,
as the system cooling is deactivated (OC/1 = 0)
CN/1
10
60
60 °C minimum temperature to avoid condensation of flue gas
OC/1
1
0
System cooling deactivated
DO/2
6
Switch-on temperature difference for 3-way-valve
reverse lifting
DF/2
4
Switch-off temperature difference for 3-way-valve
reverse lifting
SX/2
60
The 3-ay-valve is switched off as soon as the adjusted value is
reached in the heating circuit reverse.
CL/2
140
This adjustment channel has no relevance in this case.
CX/2
120
Switch-on temperature for system cooling has no influence,as
the system cooling is deactivated (OC/2 = 0)
CN/2
10
Minimum temperature limitation for reverse lifting is
deactivated
OC/2
1
0
System cooling is deactivated
MM
4
Manual mode/MM 4 = automatic operation
PG/VN
Program number/version number
temperature (SX/1). At the same time a
∆
T-reverse raising
is effected independently from the solid hot fuel boiler. If
the switch-on temperature difference (DO/2) between the
sensors S3 and S4 is exceeded, a 3-way-valve is activated
for heating circuit support by relay output R2.