background image

 
 
 
 
 
 
 
 

 

SWIMMING POOL HEAT PUMP  UNIT

 

 

Installation & Instruction Manual

 

 
 

 

Summary of Contents for Oasis C17br

Page 1: ...SWIMMING POOL HEAT PUMP UNIT Installation Instruction Manual...

Page 2: ......

Page 3: ...Swimming Pool Heat Pumps Location 5 3 3 How Close to Your Pool 5 3 4 Swimming Pool Heat Pumps Plumbing 6 3 5 Swimming Pool Heat Pumps Electrical Wiring 7 3 6 Initial Startup of the Unit 7 4 Usage and...

Page 4: ...cording to the recommended time and frequency as stated in this manual Use genuine standard spare parts only Failure to comply with these recommendations will invalidate the warranty Swimming Pool Hea...

Page 5: ...0V 50Hz Compressor Quantity 1 Compressor rotary Fan Quantity 1 Fan Power Input W 150 Fan Rotate Speed RPM 850 Fan Direction horizontal Noise dB A 56 Water Connection mm 40 Water Flow Volume m3 h 6 Wat...

Page 6: ...CATION 2 2 The dimensions for Swimming Pool Heat Pump Unit Model Oasis C17br E A G Water outlet 40 Water inlet 40 unit mm TYPE SIZE Oasis C17br A 1156 B 867 C 487 D 447 E 790 F 470 G 430 H 113 I 370 F...

Page 7: ...and the water unit the other items in the illustration are necessary spare parts for the water system that provided by users or the installer Attention Please follow these steps when using for the fi...

Page 8: ...ns deny the unit of a continuous source of fresh air which reduces it efficiency and may prevent adequate heat delivery Air outlet 800mm Air inlet 1000mm 3 3 How Close To Your Pool Normally the pool h...

Page 9: ...g at the unit inlet and outlet to allow easy draining of unit for winterizing and to provide easier access should servicing be required To pool PVC COUPLER RECOMMENDED Provided From pump CONDENSATION...

Page 10: ...3 6 Initial startup of the Unit NOTE In order for the unit to heat the pool or spa the filter pump must be running to circulate water through the heat exchanger Start up Procedure After installation...

Page 11: ...Press this button can start up or shut down the unit cancel the current operation or back to the upper interface 2 MODE SET Mode Press this button can switch modes or save parameter setting 3 Clock P...

Page 12: ...It is showed when the main display area gives the inlet water temperature measured value OUT Outlet water It is showed when the AUX display area gives the outlet water temperature measured value TEMP...

Page 13: ...one in the main interface For example Water outlet Water inlet temperature Water outlet Actual Mode display temperature Actual Mode display temperature TEMP OUT MODE SET for 0 5 second can switch betw...

Page 14: ...ng target temperature 2 4 Clock setting In the main interface press twice Hours start to flashing and press to increase value or press to decrease value and to save setting At the same time minute sta...

Page 15: ...OUT SET Press to save hour value setting Flashing TEMP IN C TEMP OUT MODE SET TEMP IN C TEMP MODE OUT SET Press to save minute value setting TEMP IN C TEMP MODE OUT SET Hour minute Flashing Flashing T...

Page 16: ...off is flashes you can set the timer off means the unit timer is off If you want cancel the timer off In the off flashing to cancel Attention 1 If there is no operation for 5s system will remember clo...

Page 17: ...TEMP IN TEMP OUT ON OFF C MODE SET Press Flashing Flashing or Flashing Flashing ON ON OFF OFF TEMP IN TEMP OUT C MODE SET Press TEMP IN TEMP OUT C MODE SET Press or Flashing Flashing The timer on and...

Page 18: ...ing of timer off For example The timer on off has been set ON is flashing ON ON TEMP OFF C Press TEMP OFF C IN IN TEMP OUT MODE SET for 2s TEMP OUT MODE SET OFF is flashing Press The setting of timer...

Page 19: ...he keyboard will be unlocked NOTES When the unit is in alarming state the key lock can be removed automaticly Hold on 2 5 Malfunction display Locked There will be malfunction code showing on the contr...

Page 20: ...eaning Default Remark Heating inlet target temp 27 Adjustable Cooling inlet target temp 27 Adjustable Auto inlet target temp 27 Adjustable Remark The wire controller can display the temperature unit a...

Page 21: ...he exhaust pressure is high high pressure switch action Check high pressure switch and cooling return circuit Low pressure protect E02 The suction pressure is low Low pressure switch action Check low...

Page 22: ...1 DI04 GND High pressure protect 12 DI05 GND No use 13 DI06 GND No use 14 AI01 GND Suction temp input 15 AI02 GND Water in temp input 16 AI03 GND Water out temp input 17 AI04 GND Temp Of coil input 18...

Page 23: ...it CANNOT be installed near the flammable gas Once there is any leakage of the gas fire can be occur 8 Make sure that there is circuit breaker for the unit lack of circuit breaker can lead to electric...

Page 24: ...A 30mA less than 0 1 sec 186 224A 2 95mm2 95mm2 280A 30mA less than 0 1 sec 2 Three phase unit Nameplate maximum current Phase line Earth line MCB Creepage protector Signal line No more than 10A 3 1 5...

Page 25: ...Fan motor 1 24 20000 220247 Handle 1 7 32009 210204 Fan motor holder 1 25 32009 210605 Right panel 1 8 32009 210253 Left panel 1 26 2004 1437 4 way reverse valve 1 9 32009 120021 Evaporator 1 27 2000...

Page 26: ...Note...

Page 27: ...Oasis Technologies Ltd Ph 09 5358891 www oasisheatpumps com...

Page 28: ...harm to the environment to human health from uncontrolled waste disposal recycle it responsibly to promote the sustainable reuse of material resources To return your used device please use the return...

Reviews: