109
en
Healthbox
®
II (Compact) & Healthbox
®
Smartzone
eco
➊
ECO
➋
HDC
➌
EmptyHouse/
Light Breeze Mode
➍
BOOST
OPERATION FAN UNIT
continu-
ously on blinking
continu-
ously on blinking
continu-
ously on blinking
continu-
ously on blinking
1
0
1
0
1
0
1
0
Fan unit will fan 30 minutes in C-Mode; afterwards, Eco Mode
will be automatically switched on
1
0
0
0
1
0
1
0
Display adjusted pressure: 220Pa
1
0
1
0
0
0
1
0
Display adjusted pressure: 260Pa
1
0
1
0
1
0
0
0
Display adjusted pressure: 200Pa
1
0
0
0
1
0
0
0
Display adjusted pressure: 140Pa
1
0
1
0
0
0
0
0
Display adjusted pressure: 120Pa
1
0
0
0
0
0
0
0
Fan unit ventilates permanently in EcoMode
0
1
0
1
0
1
0
1
System error. For Healthbox
®
II: the amount of blinks in a
sequence determines the error code
0
1
0
0
0
0
0
1
1° use, fan unit must be calibrated
0
0
0
1
0
1
0
1
Fire safety in operation - fan unit not in operation (pressureless
system with closed valves). If the safety condition no longer
applies, the system automatically reverts back to the fan mode.
0
0
0
0
0
0
0
slow
Fan unit ventilates for 10 hours in Boost Mode and then will
automatically switch to Eco Mode
0
0
1
0
1
0
1
0
Display adjusted pressure: 240Pa
0
0
0
0
1
0
1
0
Display adjusted pressure: 160Pa
0
0
1
0
0
0
1
0
Display adjusted pressure: 180Pa
0
0
0
0
0
0
0
fast
Fan unit will fan for 30 minutes in Boost Mode; afterwards,
EcoMode will automatically switch on
0
0
1
0
1
0
0
0
Display adjusted pressure: 100Pa
0
0
0
0
1
0
0
0
Depending on the settings of the fan unit (see section 8.5):
- Fan unit ventilates permanently in Empty House Mode
- Fan unit ventilates for 7 hours in Night Mode; afterwards
Eco Mode will automatically switch on
0
0
0
slow
0
0
0
0
Fan unit will fan for 2 hours in HDC Mode; afterwards,
EcoMode will automatically switch on
0
0
1
0
0
0
0
0
Fan unit ventilates permanently in HDC Mode
4 LEDs rotate
Calibration fan unit
8.4 • Display LEDs
Содержание Healthbox II
Страница 1: ...Handbuch Manual Software version 0 6 40 Healthbox II Compact Healthbox Smartzone HEALTHBOX Breeze...
Страница 61: ...de Healthbox II Compact Healthbox Smartzone 61...
Страница 121: ...121 en Healthbox II Compact Healthbox Smartzone 121...
Страница 122: ...122 Healthbox II Compact Healthbox Smartzone...
Страница 123: ...123 Healthbox II Compact Healthbox Smartzone...