43
Endura
®
Delta
en
Installer
Installer settings
It is important that you, as the installer, configure the flow rates of the
ventilation system using this menu in order to guarantee the correct
operation of the unit.
Moreover, it is advisable to then carry out the installer’s registration of the
unit. A measurement report has been integrated into the registration form,
so that you can immediately send a copy of this to the principal and EPB
reporter.
a) Flow rate settings
The nominal flow rate for the home and the intensity of the various ventilation levels can be set
using this menu.
The nominal flow rate must equal the design flow rate of the home. Thanks
to the constant flow operation of the Endura Delta, the system always
operates in a balanced manner and guarantees the flow rate.
The other levels are defined as a percentage of this nominal flow rate. By
default, the levels are programmed as follows:
Level 1 = 25%
Level 2 = 50%
Level 3 = 75%
Level 4 = 100%
− Select the desired flow rate using the slider.
− Tap “Save” if you do not wish to make any further changes.
E.g.: the design flow rate for a home is 250 m³/h, so the nominal flow rate should be set at
250 m³/h.
Level 1 = 25% = 62.5 m³/h
Level 2 = 50% = 125 m³/h
Level 3 = 75% = 187.5 m³/h
Level 4 = 100% = 250m³/h
Once the flow rates have been set, the system must be put into C-mode to check the flow rates
and fine-tune the valves.