Wiring the Output Status Relays
28
29
30
31
NormallyClosed Contact
(Form B)
NormallyClosed Contact
Common (Form B)
NormallyOpen Contact
(Form A)
NormallyOpen Contact
Common (Form A)
Both Form A and Form B contacts are rated for
250 VAC/30 VDC at 5 amps resistive or 2 amps inductive
load.
The following parameter must be set:
P.013: Output Relay Configuration
Note that depending on the setting of parameter P.013, the
relay coil will energize (the normallyopen contact will close
and the normallyclosed contact will open). Refer to the
GV3000 Programming instruction manual (D23339) for
more information.