72
Digital Input Connections (Terminals 1625)
D
Terminal 16: +24 VDC (Current Limited) (For remote control digital inputs only)
D
Terminal 17: Digital Input 8 (Remote/Local) Programmable
D
Terminal 18: Digital Input 7 (Ramp1/Ramp2) Programmable
D
Terminal 19: Digital Input 6 (Forward/Reverse) Programmable
D
Terminal 20: Function Loss
D
Terminal 21: Run/Jog
D
Terminal 22: Reset
D
Terminal 23: Stop
D
Terminal 24: Start
D
Terminal 25: +24 VDC Common
When a userinstalled function loss input, a coasttostop pushbutton, or another external interlock is
installed, the factorinstalled jumper connecting terminals 16 and 20 (or 16A and 20A) must be
removed so that a contact will open to stop the drive.
Terminals 17, 18, and 19 (remote control inputs 8, 7, and 6) are programmed using parameters P.007,
P.008, and P.031 through P.038. Factory default settings are shown here in parentheses. Refer to the
GV3000 Programming Manual (D23339) for more information.
Snubber Resistor Braking Connections (Terminals 26 and 27)
D
Terminal 26: Snubber Resistor Braking Signal (125HP Drives only)
D
Terminal 27: +24 VDC Common
Status Relay Connections (Terminals 2831)
D
Terminal 28: N.C Relay Contact
D
Terminal 29: N.C. Relay Common
D
Terminal 30: N.O. Relay Contact
D
Terminal 31: N.O. Relay Common
Relay contact closure is programmable through parameter P.013. Refer to the GV3000 Programming
Manual (D23339) for more information.