Wiring a Forward/Reverse Input
19
Digital Input 6
(Default Forward/Reverse)
Digital input 6 is control function programmable through
parameter P.007. The following parameters must be set:
P.000: Control Source
P.006: Second Menu Password
P.007: Terminal Strip Digital Inputs Configure (Selects
and assigns a control function to digital inputs 6
to 8).
P.008: Terminal Strip Speed Reference Source (Analog,
Motor Operated Potentiometer (MOP), or
Preset Speeds)
P.027: Reverse Disable
Note that based on the settings of parameters P.000, P.007,
P.008, and r.030 if an RMI board is used, the following
parameters can affect digital input 6.
P.023: MOP Accel/Decel Time
P.024: MOP Reset Configuration
P.031 to P.038: Preset Speeds 18
Refer to the GV3000 Programming instruction manual
(D23339) for additional information.
Terminal 19 On = Reverse Direction
Diagram shows factory setting. From the pulse tachometer
end of the motor, clockwise rotation indicates forward mo
tor movement.