2.7.1.2 Analog Output Jumper
Jumper J17 is the analog output jumper. This jumper selects either a 010 VDC or 420 mA scaled
signal output that is programmable for either speed or torque, parameter P.012. The jumper only
selects a 010 VDC source voltage or 420 mA sink current to represent speed or torque. Note that
the 420 mA current selection requires a power supply for operation as shown in table 7.1, terminals
10 and 11.
Use the following procedure to set jumper J17:
DANGER
DC BUS CAPACITORS RETAIN HAZARDOUS VOLTAGES AFTER INPUT POWER HAS BEEN
DISCONNECTED. AFTER DISCONNECTING INPUT POWER, WAIT FIVE (5) MINUTES FOR THE DC
BUS CAPACITORS TO DISCHARGE AND THEN CHECK THE VOLTAGE WITH A VOLTMETER TO
ENSURE THE DC BUS CAPACITORS ARE DISCHARGED BEFORE TOUCHING ANY INTERNAL
COMPONENTS. FAILURE TO OBSERVE THIS PRECAUTION COULD RESULT IN SEVERE BODILY
INJURY OR LOSS OF LIFE.
Step 1. Turn off input power to the drive and wait five minutes.
Step 2. Remove the cover from the drive by unscrewing the four attaching screws.
Step 3. Verify that the DC bus voltage is zero by following the procedure in section 9.3.
Step 4. Locate jumper J17 on the Regulator board. Refer to figures 2.8 and 2.9.
Step 5. Locate pin 1 on jumper J17. Move the jumper to the desired setting as shown in figure 2.11.
Step 6. Reattach the cover.
Step 7. Reapply input power.
Step 8. Verify that parameter P.012 is set correctly for either speed or current.
J17
J17
+10 VDC
Voltage Output Option
Pins 23
Current Output Option
Pins 12
020 mA
(default)
Figure 2.11 Jumper J17 Settings for Analog Outputs