U39-12 ULTIMATE™ Freestanding Gas Stove
|
29
installation
Gas Pipe Pressure Testing
The appliance must be isolated from the gas supply
piping system by closing its individual manual shut-
off valve during any pressure testing of the gas
supply piping system at test pressures equal to or
less than 1/2 psig. (3.45 kPa). Disconnect piping
from valve at pressures over 1/2 psig.
Conversion to High Elevation
The manifold pressure is controlled by a regulator
built into the gas control, and should be checked
at the pressure test point.
Note: To properly check gas pressure,
both inlet and manifold pressures
should be checked using the valve
pressure ports on the valve.
1. Make sure the valve is in the "OFF" position.
2. Loosen the "IN" and/or "OUT" pressure tap(s),
turning counter clockwise with a 1/8" wide flat
screwdriver.
3. Attach manometer to "IN" and/or "OUT" pressure
tap(s) using a 5/16" ID hose.
4. Light the pilot and turn the valve to "ON" position.
Read manometer.
5. The pressure check should be carried out with
the unit burning and the setting should be within
the limits specified on the safety label.
6. When finished reading manometer, turn off the
gas valve, disconnect the hose and tighten the
screw (clockwise) with a 1/8" flat screwdriver.
Note: Screw should be snug, but do not over
tighten
THIS CONVERSION MUST BE DONE BY A QUALIFIED GAS
FITTER IF IN DOUBT DO NOT DO THIS CONVERSION !!
920-140
06.27.19
1
THIS CONVERSION MUST BE DONE BY A QUALIFIED GAS FITTER
IF IN DOUBT DO NOT DO THIS CONVERSION !!
CONVERSION TO HIGH ELEVATION
Natural Gas Conversion Kit 734-920 Contains:
Qty. Part # Description
1 904-644 Burner Orifice #35 (NG)
1 918-034 Decal "Converted to 35,000 Btu"
1 920-140 Instruction Sheet
Propane Conversion Kit 734-922 Contains:
Qty. Part # Description
1 904-645 Burner Orifice #51 (LPG)
1 918-034 Decal "Converted to 32,500 Btu"
1 920-140 Instruction Sheet
1. Shut off the gas supply.
2. Open the front door. Carefully remove the logs
and media.
3. Remove burner. See diagram below.
tooltip
Note: Use a magnetic type screwdriver if
possible.
Burner Orifice
4. Remove burner orifice with a 1/2" wrench and
discard.
5. Reinstall new burner orifice (NG stamped
#35 or LP stamped #51) and tighten.
6. Reverse steps 3 and 2.
7. Attach the label "This unit has been
converted to..." on top of the Serial # decal
over the higher Btu information.
8. Check for gas leaks.
9. Check inlet and outlet pressures.
10. Check operation of flame control. Check for
proper flame appearance and glow on logs.
11. The burner aeration should be set to 3/8” open
for NG and 1/2” open for LP. See aeration
adjustment details in the manual.