26
|
City Series CST60E
installation - general
Shown with ventilation openings on the front to meet the minimum requirement of
120 sq. in.
Flush Installation Examples (Ventilation Openings)
Option 1 - Front
IMPOR
TANT
• When creating any type of ventilation opening, measures should be taken to prevent objects falling or being thrown into
the ventilation opening. Mesh screen, louvers, or other protection should be used.
• If the ventilation openings are placed in two rooms (two different pressure zones), the ventilation openings must have
equally split air openings to balance air flow.
A
B
D
C
A
10" (154 mm) min.
B
2" (51 mm) max.
C
120 sq in min.
D
1-1/2" (38 mm) min.
Option 2 - Front/Side
Shown with ventilation openings on side and front to meet the minimum requirement
of 120 sq. in.
A
10" (254 mm) min.
B
2" (51 mm) max.
C
120 sq. in. min.
D
4" (102 mm) min.
E
10" (254 mm) min.
F
1-1/2" (38 mm) min.
A
B
C
D
B
E
F