City Series CST60E
|
21
installer's information
NO
TE
• See section "Exterior Vent Termination
Locations."
A
Glass
B
Glass
C
36" min. (914 mm)
D
36" min. (914 mm)
E
36" min. (914 mm) walkway
F
36" min. (914 mm) walkway
Locating Your Gas Fireplace
1. When selecting a location for your fireplace, ensure
that the clearances are met as outlined in the
"Clearances" section.
2. Provide adequate clearances for servicing.
3. The appliance must be installed on a flat, solid,
continuous surface (e.g. wood, metal, concrete).
This may be the floor, or a platform to enhance
visual impact. If the appliance is going to be installed
on carpeting, combustible linoleum tile, or other
combustible material (other than wood flooring),
the appliance must be installed on a metal or
wood panel extending the full width and depth of
the appliance.
4. This Direct Vent Gas Fireplace can be installed as
follows:
Position
Model #
A, B
CST60E See-through
5. This appliance is listed for bedroom installations
when used with a listed millivolt thermostat. Some
locations may have further requirements - check
local codes before installation.
6. The CST60E Direct Vent Gas Fireplace is approved
for alcove installations which meet the clearances
listed on this page.
7. We recommend that you plan your installation on
paper using exact measurements for clearances
and floor protection. Have a qualified inspector,
dealer, or installer review your plans before
installation.
A. CST60E - SEE-THRU
B. CST60E - SEE-THRU
A
B
C
D
E
A
B
C
D
F