30
|
City Series CST60E
installation - general
Bench Installation Examples (Ventilation Openings)
Option 1 - Top
Shown with ventilation opening on top of the enclosure to meet the minimum require-
ment of 180 sq. in.
IMPOR
TANT
• When creating any type of ventilation opening, measures should be taken to prevent objects falling or being thrown into
it. Mesh screen, louvers, or other protection should be used.
• **If the ventilation openings are placed in two rooms (two different pressure zones), the ventilation openings must have
equally split air openings to balance air flow.
A
B
C
D
A
10" (254 mm) min.
B
180 sq. in. min.
C 1-1/2" (38 mm) min.
D 3" (77 mm) min.
A
B
C
D
Option 2 - Front and Back
Shown with ventilation openings on the front and back of the enclosure to meet the
minimum requirement of 180 sq. in.
A
10" (51 mm) min
B
2" (51 mm) max.
C 90 sq. in. front and back
D 1-1/2" (38 mm) min.