Maintenance
72 — English
Servitec 35-120 with Touch controller — 06.07.2016 - Rev. B
10.5
Inspection
10.5.1
Pressure-bearing components
Comply with all applicable national regulations for the operation of pressure equipment. De-pressurise all pressurised components prior
to inspection (see disassembly information).
10.5.2
Inspection prior to commissioning
In Germany, follow the Industrial Safety Regulation [Betriebssicherheitsverordnung] Section 15 and Section 15 (3) in particular.
10.5.3
Inspection intervals
Recommended maximum inspection intervals for operation in Germany pursuant to Section 16 of the Industrial Safety Regulation
[Betriebssicherheitsverordnung] and the vessel classification of the device in diagram 2 of the Directive 2014/68/EC, applicable in strict
compliance with the Reflex Installation, Operation and Maintenance Manual.
External inspection:
No requirement according to Annex 2, Section 4, 5.8.
Internal inspection:
Maximum interval according to Annex 2, Section 4, 5 and 6; if necessary, suitable replacement actions are to be taken (such as wall
thickness measurement and comparison with the design specification which may be requested from the manufacturer).
Tightness test:
Maximum interval according to Annex 2, Section 4, 5 and 6.
Furthermore, compliance with Section 16 of the Industrial Safety Regulation and Section 16 (1) in particular, in conjunction with Annex
2, Section 4, 6.6 and Annex 2, Section 4, 5.8, must be ensured.
The actual intervals must be determined by the user on the basis of a safety-technical assessment taking into account the real
operational conditions, the experience with the operation and the charging material, and the national regulations for the operation of
pressure equipment.