Controller
54 — English
Servitec 35-120 with Touch controller — 06.07.2016 - Rev. B
3. Select the required language and conform your entry with
"OK".
•
You can select between 16 different languages.
Start routine Step 3
(001) Language
German
English
2.2 bar
Continuous degassing
4. Select the calculated minimum operating pressure and
conform with "OK".
– For calculation of the minimum operating pressure, see
chapter 7.2 "Setting the minimum operating pressure
for Magcontrol" on page 37 .
Start routine Step 5
(005) Min. operating pressure p0
1.8 bar
2.2 bar
Continuous degassing
5. Set the time. The time of an alarm will be stored in the
controller's fault memory.
– Use the "Left" and "Right" buttons to select the display
value.
– Use the "Up" and "Down" buttons to change the display
value.
– Confirm your entries with "OK".
Start routine Step 7
(002) Time
09:30
2.2 bar
Continuous degassing