Configuring settings in the controller
You can configure the controller settings regardless of the currently selected and active operating mode.
9.4.1
Customer menu
9.4.1.1
Customer menu – overview
Use the Customer menu to correct or determine system-specific values. In the course of commissioning, the factory settings must be
adjusted for the system-specific conditions.
Note!
For a description of the operation, see chapter 9.1 "Operator panel" on page 51 .
A three-digit PM code is assigned to the setting options.
PM code
Description
001
Select the language
002
Set the time
003
Set the date
Select the system type
•
Levelcontrol
•
Magcontrol
005
Set the "P
0
" minimum operating pressure, see chapter 7.2 "Setting the minimum operating pressure for Magcontrol"
on page 37 .
006
Set the actuating pressure for the system safety valve.
– The actuating pressure protects the device.
Degassing
˃
010
•
Degassing programme
•
Continuous degassing
•
Interval degassing
•
Run-on degassing
011
•
Continuous degassing time
Make-up >
023
•
Maximum make-up time …min.
024
•
Maximum make-up cycles … /2 h.
– Frequency of make-up cycles in 2 hours.
024
•
Make-up pressure for the Magcontrol make-up variant.
– Standard = Make-up pressure
˃
1.3 bar.
– Setting range 1.3 – 2.3 bar.
– < 1.3 bar.
027
•
With contact water meter "Yes/'No".
– If "Yes", continue with 028.
– If "No", continue with 007.
028
•
Reset make-up quantity "Yes/No".
– If "Yes", reset to "0".
029
•
Maximum make-up quantity ... l
030
•
With softening "Yes/'No".
– If "Yes", continue with 031.
– If "No", continue with 007.