Commissioning
36 — English
Servitec 35-120 with Touch controller — 06.07.2016 - Rev. B
7
Commissioning
CAUTION
Risk of burns on hot surfaces
Hot surfaces in heating systems can cause burns to the skin.
•
Wear protective gloves.
•
Please place appropriate warning signs in the vicinity of the device.
Note!
Confirm that installation and start-up have been carried out correctly using the installation, start-up and maintenance
certificate. This action is a prerequisite for the making of warranty claims.
– Have the Reflex Customer Service carry out commissioning and the annual maintenance.
7.1
Checking the requirements for commissioning
The device will be ready for commissioning when the tasks described in the "Installation" chapter have been completed.
•
The device has been mounted.
•
The connections of the device to the system has been created and the facility system pressure maintenance is operational.
– Degassing line to the facility system.
– Degassing line from the facility system.
•
The water-side connection of the device to the make-up has been created and is operational, if automatic make-up is required.
•
The connection pipes of the device have been purged and cleaned of welding residue and dirt before commissioning.
•
The entire system is filled with water and all gases have been vented in order to ensure a circulation through the entire system.
•
The electrical connection has been created according to applicable national and local regulations.