Commissioning
Servitec 35-120 with Touch controller — 06.07.2016 - Rev. B
English — 43
Proceed as follows:
1. Use a screwdriver to undo the locking screws at the caps of
the overflow valve (1).
2. Use a screwdriver to undo the locking screws at the caps of
the pressure-reducing valves (2, 3).
Complete the hydraulic equalisation of the system degassing:
3. Touch "Manual mode" on the controller's operator panel.
4. Touch "Circulating" on the controller's operator panel.
•
The pump is switched on. Continuous degassing is
activated.
Servitec
Filling
Wv.
CD
PU
Circulate
2.2 bar
Continuous degassing
When the vacuum gauge at the vacuum spray pipe indicates a
stable vacuum, turn the caps at the pressure-reducing valves (2,
3) and the overflow valve (1) to adjust the pressure:
•
Clockwise turning increases the pressure.
•
Counter-clockwise turning decreases the pressure.
5. Set the overflow valve (1) to the setpoint.
•
Take the setpoint for the setting from the "Technical
Data" chapter (overflow valve setpoint (bar)).