Controller
Servitec 35-120 with Touch controller — 06.07.2016 - Rev. B
English — 53
9.3
Modifying the controller's start routine
The start routine is used to set the required parameters for the device commissioning. It commences with the first activation of the
controller and can be run only once. Parameters can be changed or checked in the customer after the start routine has terminated, see
chapter 9.4.1 "Customer menu" on page 56 .
A three-digit PM code is assigned to the setting options.
Step
PM code
Description
1
Start of the start routine
– Device type information.
2
004
Select the water make-up variant
•
Levelcontrol
– Level-dependent make-up with a pressure maintaining station.
– No automatic make-up.
•
Magcontrol
– Pressure-dependent make-up with a pressure expansion tank.
3
001
Select the language
4
Remember: Prior to installation and commissioning, read the operating manual!
5
005
Set the minimum operating pressure P
O
, see chapter 7.2 "Setting the minimum operating pressure for
Magcontrol" on page 37 .
6
006
Opening pressure of the safety valve
7
002
Set the time
8
003
Set the date
9
End of the start routine. The stop mode is active.
The system automatically displays the first page of the start routine when you switch on the device for the first time.
1. Press "OK“.
– The start routine moves to the next page.
Start routine Step 1
Start routine for
system commissioning!
System type:
Servitec - 35
2.2 bar
Continuous degassing
2. Select the required water make-up mode and confirm with
"OK".
– For calculation of the make-up variant, see chapter 6.4
"Switching and make-up variants" on page 27 .
Start routine Step 2
Levelcontrol
Magcontrol
2.2 bar
Continuous degassing