Description of the device
Vacuum spray degassing — 03.11.2014
English — 13
Make-up variants
There are two make-up variants. Both are monitored via the make-up time and the make-up cycles.
000166_001_R001
230V
WC
M
DV
DC
M CD
DC
PIS
LIS
V
1
2
3
4
5
6
7
8
11
10 9
1
"WC" make-up line
7
"DC" degassing line (degassed water to the facility
system)
2
Optional add-on device (see Chapter Optional
equipment and accessories)
8
"DC" degassing line (gas-rich water from the facility
system)
3
Device
9
"CD" 3-ways motor ball valve
4
"DV" degassing valve
10
Device controller
5
"PU" vacuum pump
11
Signal line from the "LIS" level sensor of a pressure
maintaining station
6 "PIS"
pressure
transducer from the device
Magcontrol:
For systems with diaphragm-type pressure expansion tank.
– Using the integrated "PIS" pressure sensor, the system registers and monitors the pressure in the
heating or cooling system. The make-up degassing process is activated as soon as the pressure drops
below the calculated filling pressure.
Levelcontrol:
For systems with pressure maintaining stations.
– The pressure maintaining station uses the "LIS" pressure pick-up to determine the water level in the
expansion tank. The make-up function is triggered by a 230 V signal.
Note!
Ensure the correct connection of the device to the facility system.
– For the Levelcontrol make-up variant in particular, the signal line from the level sensor of the pressure maintaining
station must be connected to the device.