Operation
42 — English
Vacuum spray degassing — 03.11.2014
ER Code
Alarm
Floating
contact
Cause
Remedy
Alarm reset
06
Make-up time
-
•
Set value exceeded.
•
Water loss in the system
• Make-up
line
not
connected.
•
Make-up rate insufficient.
•
Make-up hysteresis too
low.
•
Check set value in
the Customer or
Service menu.
•
Check water level.
• Connect
"WC"
make-up line.
Quit
07
Make-up cycles
-
Set value exceeded.
•
Check set value in
the Customer or
Service menu.
•
Seal the leak in the
system.
Quit
08 Pressure
measurement
-
For "Magcontrol" setting only.
• Controller
receives
incorrect signal.
•
Connect the plug.
•
Check the cable for
damage.
•
Check the pressure
transducer.
Quit
10
Maximum pressure
-
For "Magcontrol" setting only.
• Set
value
exceeded.
•
Check set value in
the Customer or
Service menu.
•
Set the tripping
pressure of the
safety valve.
-
11
Back-up volume
-
"With water meter" must be
activated in the Customer
menu.
• Set
value
exceeded.
•
Severe water loss in the
system.
•
Check set value in
the Customer or
Service menu.
•
Check the water
loss and correct, if
necessary.
Quit
14
Discharge period
-
•
Set value exceeded.
•
"DC" degassing line closed.
•
Dirt trap clogged.
•
Check set value in
the Customer or
Service menu.
•
Open the "DC"
degassing line.
•
Clean the dirt trap.
Quit
15 Back-up
valve -
Contact water meter measures
without make-up request.
Check the "CD" 3-ways
ball valve for leaks.
Quit
16
Power failure
-
No power.
Connect to power.
-