Commissioning
32 — English
Vacuum spray degassing — 03.11.2014
7.4.2
Modifying the controller's start routine
The start routine enables the setting of the essential parameters required for the device's commissioning. It commences with the first
activation of the controller and can be run only once. Parameters can be changed or checked in the customer after the start routine has
terminated see chapter 7.4.3 "Parametrising the controller" on page 33 .
Notice!
Plug in the contact plug to provide power (230 V) to the controller.
You are now in Stop mode. The "Auto" LED on the operator panel has extinguished.
Magcontrol:
Select this setting if you want to realise a pressure-dependent automatic make-up in a
system with diaphragm expansion tank.
Levelcontrol:
Select this setting if you want to operate a level-dependent make-up in a system with
pressure maintenance station.
Servitec
Magcontrol
Standard software with various languages.
Language
Prior to commissioning, read the entire operating manual and verify the proper assembly.
Read the operating manual!
Only displayed if "Magcontrol" has been selected in the "Servitec" menu option.
P0 calculation, see chapter 7.2 "Setting the minimum operating pressure for Magcontrol"
on page 29 .
Min. op. pressure
Only displayed if "Magcontrol" has been selected in the "Servitec" menu option.
– Specify the tripping pressure of the applicable safety valve for the device protection.
This is usually the safety valve at the system heat generator.
Safety valve pressure
Change the flashing display items for "Hour", "Minute", and "Seconds" to the current time.
The time of an alarm will be stored in the fault memory.
Time:
Change the flashing display items for "Day", "Month", and "Year" to the current date.
The date of an alarm will be stored in the fault memory.
Date:
Select in the message line and confirm with "OK":
Terminate start routine?
yes:
The start routine is terminated. Servitec automatically switches to stop mode.
no:
The start routine restarts.
The pressure is displayed only in "Magcontrol" mode.
2.0 bar
STOP
Notice!
You are in Stop mode. Please do not switch from the start routine to Automatic mode after entering the parameters.