56
Set
Stop
Start
out1
1
2
h:m
m:s
56
12-MENU ENTRIES AND OPERATION
ASH EVACUATION SYSTEM (THE FEED SCREW IS ACTIVATED TO AUTOMATICALLY REMOVE ASH)
1
IF IT IS ON THE SET COUNT WILL BE RUNNING, WHICH MEANS THAT THE AUTOMATIC CLEANING FUNCTION IS
ACTIVATED
Time value set by default is 5’ (the parameter can be changed from 5’ to 0’)
2
WAITING TIME BETWEEN ONE CLEANING CYCLE AND THE NEXT HOURS/MINUTES
Time value set by default is 1h 30’ (the parameter can be changed from 1h 30’ to 0’’)
SET
CONFIRM
STOP
MANUALLY DEACTIVATE THE CLEANING FUNCTION
START
MANUALLY ACTIVATE THE CLEANING FUNCTION
OUT1
LED 1 ON IF THE AUTOMATIC CLEANING FUNCTION IS ACTIVATED
The ash removal system starts automatically after the boiler heats up after being switched on and is deactivated after
cooling when shut down.
The display is powered on when the boiler is turned on. The automatic ash clearing system is therefore immediately activated with the
set default values.
If necessary, the user can change the values within the available ranges (see table above).
Change them, if necessary, as follows:
• press STOP to stop the current count
• if you press SET, the icon appears and the default value appears (in this case 5’). Modify the value by pressing the values with
the arrows (near Stop and Start)
• press SET to confirm
• then the key comes on and shows the default value (in this case 1h 30’). Change the value by pressing the keys with the arrows
(near Stop and Start)
• press SET to confirm
• press START to start a new count for the automatic cleaning cycle
Caution! If there is a power cut, when the boiler is powered back on the panel will beep and it will then restart the
cleaning count.
1
2