UM-1096
Revision A
31
Alarm 2 Trip
43012
Selection
3
6/16
1
0-High
1-Low
Alarm 2 On Delay
43013
Integer
3
6/16
1
Activation delay in seconds
Alarm 2 Off Delay
43014
Integer
3
6/16
1
Deactivation delay in minutes
Alarm 2 Deadband%
43015
Integer
3
6/16
1
Percent of scale
Alarm 2 Color
43016
Selection
3
6/16
1
0-Red
1- Orange
2-Blue
Alarm 3 Latch
43021
Selection
3
6/16
1
0-No
1-Yes
Alarm 3 Trip
43022
Selection
3
6/16
1
0-High
1-Low
Alarm 3 On Delay
43023
Integer
3
6/16
1
Activation delay in seconds
Alarm 3 Off Delay
43024
Integer
3
6/16
1
Deactivation delay in minutes
Alarm 3 Deadband%
43025
Integer
3
6/16
1
Percent of scale
Alarm 3 Color
43026
Selection
3
6/16
1
0-Red
1- Orange
2-Blue
Alarm 3 Enabled
43027
Selection
3
6/16
1
0-No
1-Yes
Data From
43031
Selection
3
6/16
1
0-Sensor
1-Remote Sensor
2-4-20mA
Min Raw
43032
Unsigned
Integer
3
6/16
1
Binary (800)
Max Raw
43033
Unsigned
Integer
3
6/16
1
Binary (4000)
Remote ID
43034
Integer
3
6/16
1
Binary
Remote ID
43042
Integer
3
1
Decimal Points
43079
Selection
3
6/16
1
Number of decimal points
Deadband(%)
43081
Integer
3
16
1
Modbus 32-bit IEEE 754
Floating Pt
Filter Count
43090
Integer
3
6/16
1
Binary ;0 to 60
Polarity
43092
Selection
3
6/16
1
Binary
Bridge Voltage
43093
32-Bit
Floating Point 3
16
2
Modbus 32-bit IEEE 754
Floating Pt
Balance
43095
Integer
3
6/16
1
Binary
Heater Enabled
43096
Selection
3
6/16
1
0-No
1-Yes
Heater Setpoint
43097
32-Bit
Floating Point 3
16
2
Modbus 32-bit IEEE 754
Floating Pt
Содержание 10-0517
Страница 4: ...UM 1096 Revision A III Drawings 44...
Страница 10: ...UM 1096 Revision A 5 Figure 2 Remote Sensor Enclosure Mounting Dimensions...
Страница 26: ......
Страница 49: ...UM 1096 Revision A 44 Appendix 9 Drawings Drawings Figure 13 Mounting Dimensions...
Страница 50: ...UM 1096 Revision A 45 Figure 14 10 0517 CPU Board Figure 15 10 0533 I O Board...
Страница 51: ...UM 1096 Revision A 46 Figure 16 10 0532 Modbus Relay Board...