UM-1096
Revision A
30
Channel Registers
Input Registers
Tag
Address Type
Function
Code to
Read
Function
Code to
Write
Size Notes
Alarm 1 Status
33017
Selection
4
N/A
1
0-No
1-Yes
Alarm 1 Flashing
33018
Selection
4
N/A
1
0-No
1-Yes
Alarm Status
33019
Selection
4
N/A
1
0-No
1-Yes
Alarm Flashing
33020
Selection
4
N/A
1
0-No
1-Yes
Alarm 3 Status
33021
Selection
4
N/A
1
0-No
1-Yes
Alarm 3 Flashing
33022
Selection
4
N/A
1
0-No
1-Yes
Fault Status
33023
Selection
4
N/A
1
0-No
1-Yes
Comm Error
33024
Selection
4
N/A
1
True if comm error
Config Error
33025
Selection
4
N/A
1
True if config error
I/O Error
33026
Selection
4
N/A
1
True if input/output error
Calibration Flag
33027
Selection
4
N/A
1
True if calibration in progress
Error Flashing
33030
Selection
4
N/A
1
True if channel error
Value
33065
32-Bit
Floating Point 4
N/A
2
Holding Registers
Tag
Address Type
Function
Code to
Read
Function
Code to
Write
Size Notes
Alarm 1 Latch
43001
Selection
3
6/16
1
0-No
1-Yes
Alarm 1 Trip
43002
Selection
3
6/16
1
0-High
1-Low
Alarm 1 On Delay
43003
Integer
3
6/16
1
Activation delay in seconds
Alarm 1 Off Delay
43004
Integer
3
6/16
1
Deactivation delay in minutes
Alarm 1 Deadband% 43005
Integer
3
6/16
1
Percent of scale
Alarm 2 Latch
43011
Selection
3
6/16
1
0-No
1-Yes
Содержание 10-0517
Страница 4: ...UM 1096 Revision A III Drawings 44...
Страница 10: ...UM 1096 Revision A 5 Figure 2 Remote Sensor Enclosure Mounting Dimensions...
Страница 26: ......
Страница 49: ...UM 1096 Revision A 44 Appendix 9 Drawings Drawings Figure 13 Mounting Dimensions...
Страница 50: ...UM 1096 Revision A 45 Figure 14 10 0517 CPU Board Figure 15 10 0533 I O Board...
Страница 51: ...UM 1096 Revision A 46 Figure 16 10 0532 Modbus Relay Board...