Output Settings
Output Settings Menus
Analog Outputs
o
Fault mA
Allows the user to configure the mA output when the
detector is in the Fault condition. This is useful to indicate a
fault condition on the connected control device.
o
Cal mA
Allows the user to configure the mA output when the
detector is in Cal Mode. This is useful to indicate a
calibration condition on the connected control device.
Relay 1, 2, 3
o
Source
The Source setting can be set to Alarm 1, Alarm 2, Alarm 3,
Fault, Cal Mode, Cal Zero, Cal Span or Disabled. This setting
determines which condition must be met in order for the
relay to actuate.
o
Failsafe
When set to Yes, Failsafe means the relay de-energizes
during alarm and energizes with no alarm. This is useful for
signaling an alarm on a loss of power. The dedicated Fault
relay is always Failsafe.
o
Acknowledge
When set to Yes, Acknowledge means the
UP/RESET
key will
set the relay to its normal state even if the alarm condition
still exists. This can be useful for silencing audible devices
driven from the relay.
o
Refresh
When enabled, this feature refreshes the relay for
acknowledged alarms if the indicated time elapses and the
alarm condition still exists
o
State
Indicates the current state of the relay
Inhibit
o
Fault mA
The inhibit feature allows the user to inhibit outputs during a
designated time period. Once the timer has been started all
outputs will be blocked until the time has expired.
o
Start Inhibit
Starts the inhibit timer
o
Stop Inhibit
Stops the inhibit timer
o
Timer (s)
Indicates the time remaining on the inhibit timer in seconds
Out put Set t i ngs
Anal og Out put >
Rel ay 1 >
Rel ay 2 >
Rel ay 3 >
I nhi bi t >
Anal og Out put s
Faul t mA 1
Cal mA 3
Rel ay 1
Sour ce Al ar m 1
Fai l saf e No
Acknowl edge No
Ref r esh( m) No
St at e Cl ear
Rel ay 2
Sour ce Al ar m 2
Fai l saf e No
Acknowl edge No
Ref r esh( m) No
St at e Cl ear
Rel ay 3
Sour ce Faul t
St at e Cl ear
I nhi bi t
I nhi bi t Ti me( m) 15
St ar t I nhi bi t >
St op I nhi bi t >
Ti mer ( s) 0
Содержание 10-0517
Страница 4: ...UM 1096 Revision A III Drawings 44...
Страница 10: ...UM 1096 Revision A 5 Figure 2 Remote Sensor Enclosure Mounting Dimensions...
Страница 26: ......
Страница 49: ...UM 1096 Revision A 44 Appendix 9 Drawings Drawings Figure 13 Mounting Dimensions...
Страница 50: ...UM 1096 Revision A 45 Figure 14 10 0517 CPU Board Figure 15 10 0533 I O Board...
Страница 51: ...UM 1096 Revision A 46 Figure 16 10 0532 Modbus Relay Board...