Fire Alarm Control Panel 

 

 

 

 

 

Installation, Commissioning & Operating 

user Manual

 

 

 

 

 
 
 
 
 
 
 

Содержание RE-900

Страница 1: ...RE 900 Fire Alarm Control Panel Installation Commissioning Operating user Manual...

Страница 2: ...indicated that smoke detectors may not go off in as many as 35 of all fires While fire alarm systems are designed to provide early warning against fire they do not guarantee warning or protection agai...

Страница 3: ...escaping gas improper storage of flammable materials etc While a fire alarm system may lower insurance rates it is not a substitute for fire insurance Heat detectors do not sense particles of combusti...

Страница 4: ...atible with the control It is essential to use only equipment listed for service with your control panel Telephone lines needed to transmit alarm signals from a premise to a central monitoring station...

Страница 5: ...4 RE DD UM RE 900 1 0 0 NOTES...

Страница 6: ...CATIONS 16 2 3 1 CONTROLS 16 2 3 2 INDICATIONS 17 2 3 2 1 LED INDICATIONS 17 2 4 MECHANICAL CONSTRUCTION 18 CHAPTER 3 INSTALLATION 22 3 1INSTALLATION PRECAUTION 22 INSTALLATION PRECAUTIONS 22 CHAPTER...

Страница 7: ...l equipment 1 2 General The panel is self contained with integral power supply and space provision for two sealed lead acid standby batteries and comply with the requirements of IS 2189 1988 The panel...

Страница 8: ...m as described later To Evacuate the premises Press the Evacuate key and enter the password to OPERATE SOUNDERS Fault Indication If the control panel indicates a Fault condition make a note of all ill...

Страница 9: ...e tested each week Record and report any malfunction Quarterly The responsible person should ensure that every three months the system is checked by a competent person Check the standby batteries and...

Страница 10: ...9 RE DD UM RE 900 1 0 0 Mother Board Terminals and connectors Power Supply Board Terminals and connectors...

Страница 11: ...10 RE DD UM RE 900 1 0 0...

Страница 12: ...ut devices like 2 wire smoke detectors pull stations and other normally open contact devices The Outputs include notification appliance circuits NACs sounders Two Form C relays for Fire and one relay...

Страница 13: ...ppliance Circuits NAC NAC shall be programmed as auto silence Silence Inhibit Standby battery backup 24v DC power supply with builtin charger Error free Fire Fault status in unambiguous colored LED in...

Страница 14: ...ring circuits are supervised Zone Isolation facility with loop voltage cut off Earth fault annunciation facility at 0 ohms Programmable AC loss delay Programmable Trouble reminder Peer to Peer Network...

Страница 15: ...28 0v 0 5V Charging Current as required Charging Capacity 7 Amp Hour Battery Higher size are request System Quiescent Current 50mA 4 4 6 8mA per zone D C output Operating Voltage 24VDC Resettable Stea...

Страница 16: ...Operating Nominal Voltage 24 VDC Special Application Current for all NACs 2A 1 A per Circuit Line Drop 1 8V End Of Line Resistor 4K7 1 2 watt Common Relays Type Form C No of Relays 2 Relay Contact Rat...

Страница 17: ...or Admin password protected SILENCE Key To silence the external NACs in Fire Condition User or Admin password protected RESET Key To reset the particular zones in Fire alarm or Latched Supervisory co...

Страница 18: ...r Fault Yellow Mains Fail Yellow System Fault Yellow Battery Fault Yellow Earth Fault Yellow Silenced Yellow NAC Fault Yellow Zone Disable W T Yellow 2 3 2 1 LCD Indication The LCD is mainly used for...

Страница 19: ...gauge 1 22mm CRCA sheet with powder coated finish The 19mm 20No s for Indian Std 20no s of knockouts are given for cable entry at the top of the cabinet The lockable hinged door is provided to access...

Страница 20: ...19 RE DD UM RE 900 1 0 0 2 6 Internal Arrangement...

Страница 21: ...er Board RE 900 16Z MB The Master board contains the primary components and wiring interface connectors Display Board RE 900 DISP R1 1 The Display Board contains the system CPU LED Display LCDunit and...

Страница 22: ...21 RE DD UM RE 900 1 0 0 Power Supply Board RE 900 PS...

Страница 23: ...any change addition or deletion of system components or after any modification repair or adjustment to system hardware or wiring All components circuits system operations or software functions known t...

Страница 24: ...ge circuits Remove all electronic assemblies prior to any drilling filing reaming or punching of the enclosure When possible make all cable entries from the sides or rear Before making modifications v...

Страница 25: ...one is supervised for opens and ground faults Both conditions are visually and audibly toggle tone annunciated Each zone is a Class B Initiating Device Circuit IDC Zones designed to accept any normall...

Страница 26: ...ble Power 500mA 24 VDC filtered nonresettable power can be obtained from 24v DC out Terminals Sounder Circuits The RE 900 provides Notification Appliance Circuits NAC standard as Class B This circuit...

Страница 27: ...panel provides three Form C relays rated for 2 0 amps 30 VDC and 2 0 amps 30 VAC Relay connections may be power limited or nonpower limited provided that a minimum of 0 25 is maintained between conduc...

Страница 28: ...ne 3 Nacs 2 Re lay 4 24 V O P 5 Common Progra m 1 2 2 4 1 1 V ie w A ll Eve nts 2 A la rm Even ts 3 Delete His tory 1 Mode 2 L oca tio n Pro gram 3 W irin g Zone 1 Rela y 1 Fire 2 Rela y 2 Fa ult Rel...

Страница 29: ...e 2 First Floor Edit Zone 2 Second Floor B wing 2 3 A A B 1 2 1 2 Mode Tempora l Edit S ave NAC1 Mode Synchronized Edit Save NAC1 D 1 Caption 2 Date Time 3 Pas sw ord Se ttin g 1 Cap tio n Rav el Ele...

Страница 30: ...3 1 Fire O P Disab led N W O P FR Fire O P Enable N W O P FR 1 Fau lt O P Disable d N W O P FT Fa ult O P En able N W O P FT 2 NA C s O P Disab led N W O P NA C Fau lt O P Enable N W O P NA C 3 En ter...

Страница 31: ...Re Type New chg Usr1 Pass Re Type New New Password updated Press to chge 1 USER PASSWORD 1 User1 4 User4 2 User2 5 USer5 3 User3 User Pass 2 ADMIN PASSWORD Old Password Chg Adm Pass New Password Chg...

Страница 32: ...ers into View mode and shows the viewing category options as like below 1 Suppressed Events 2 History View 4 2 1 1 Suppressed Events Suppressed Events option is used to view the suppressed events duri...

Страница 33: ...nto program mode This mode is protected by password and it requires admin password Default 54321 In this mode changing the zone Relay NAC and password setting can be changed or modified After entering...

Страница 34: ...rsors goes to next line Then enter the location using the number letter key pad press ENTER key after entering location Enter Zone No AA Press to change Press Enter to Set Zone 1 Loc not entered 4 2 2...

Страница 35: ...y screen It Displays as follows 1 Type Fire Relay O P1 4 2 2 3 1 NAC 1 The NAC1 output can be configured as Temporal Synchronized Continuous 60 BPM In Temporal and synchronize mode the NAC1 output wil...

Страница 36: ...he 24V output can be configured as Resettable or steady If four wire detectors are used in the panel then the 24V DC output should be configured as Resettable While resetting the panel this output wil...

Страница 37: ...onics Edit Caption 4 2 2 5 2 Date Time By selecting the number 2 from the setting screen the system enters into RTC settings mode In this mode time and date settings are changed by using key After ent...

Страница 38: ...Pass Re type New Password Chg XXX Pass New Password Updated Press to change 4 2 2 5 3 2 Admin Password From the Admin Password Mode screen By pressing the enter key from the change Admin Password scre...

Страница 39: ...will activate The factory default option for this feature is Enabled the trouble relay activation on AC loss after the time delay setting Press Change key to toggle between enabled disabled option Th...

Страница 40: ...munication 2 Password Control 3 Factory Default Advanced By selecting the number 1 from the Advanced screen the system enters into communication mode In this mode network and repeater configuration ca...

Страница 41: ...tput Config By selecting the number 3 from the network screen the system enters into the network Output configuration After entering into this mode screen will as shown below 1 Fire O P Disabled 2 Fau...

Страница 42: ...rd should be five digit Old Pass w ord Chg Co nfig Pas s Ne w Pa ssw ord Chg Config Pass Re Ne w Pa ssw ord Chg Config Pas s Re New Pass w ord Updated 4 2 2 4 3 2 Factory Default By selecting the numb...

Страница 43: ...te and Enter keys SILENCE Key This key is used in Fire Fault Condition To acknowledge the external sounder internal buzzer press this key And the internal buzzer tone is changed from continues tone to...

Страница 44: ...acknowledge the buzzer tone during the fault and fire condition This key can be operated with user or admin password 5 2 Indications SYSTEM ON This LED will glow when the panel is energized by primary...

Страница 45: ...fault can be created through 0 Ohms resistor SYSTEM FAULT Glowing of this LED indicates the failure of the CPU SILENCED This LED will glow when the silence key is pressed in fire condition only NAC F...

Страница 46: ...om the specific fault identification LED common fault common fault relay and Local buzzer with intermittent tone will be activated During this time if ACK is activated intermittent tone will be silenc...

Страница 47: ...The FIRE LED indication will remain ON condition till the panel is RESET Note 1 The Fire and Fault relay will be in ON condition till the fire and fault LED s go OFF 2 By silencing hooters are switche...

Страница 48: ...considered as actual fire and it comes out from the walk test mode The LCD Display is as shown below For More than One zone in Walk test fire condition the screen as follows Note a If there is no more...

Страница 49: ...e the screws of PCB which has to be change and remove the PCB from the mounting position and place the new PCB in that same position as shown below Mounting position for Main Circuit board RE 900 16Z...

Страница 50: ...for Display board RE 900 DISP R1 1 PCB Mounting Hole Door Fixing Screws PCB Mounting Hole Mounting position for Display board RE 900 PS Cable Entry Knock out Zone Board Mounting Hole Power Supply Moun...

Страница 51: ...eed the rated value Check number of detectors connected in the loop Total detectors current should not go above 2 5mA Hooter fault indication There is no proper connection in the hooter Or loop Fault...

Страница 52: ...ent DC Direct Current CRCA Cold Rolled Carbon Alloy LED Light Emitting Diode O P Output IP 54 Industrial Protection mm millimeter no s number s v volt s Ah Ampere per hour IEE Institute of Electrical...

Страница 53: ...52 RE DD UM RE 900 1 0 0 Ravel Electronics Pvt Ltd 150A Electronic Industrial Estate Perungudi Chennai 600096 India Web www ravelfire com Email marketing ravelfire com...