54
SFK 55 - RAD - ING - Manual - 1512.2_CSA_TTS
2. MAINTENANCE
SUPPOR
T CENTER
CODE
FAULT
POSSIBLE CAUSE
SOLUTION
RESET
E02
WATER TEMP. HIGH
LIMIT SWITCH 203 °F
(95°C)
THERMOSTAT CABLE
DISCONNECTED;
CHECK THE WIRING:
MANUAL RESET
(PRESS THE RESET
‘
’ KEY).
BROKEN HIGH LIMIT.
REPLACE IT.
E03
EXHAUST SAFETY HIGH
LIMIT SWITCH
216°F (102°C)
HIGH LIMIT BROKEN;
REPLACE IT;
MANUAL RESET
(PRESS THE RESET
‘
’ KEY).
HIGH LIMIT CABLE
DISCONNECTED.
CHECK THE WIRING.
E05
DOMESTIC INLET
TEMP. PROBE
(COLD WATER)
BROKEN OR INCORRECTLY
CALIBRATED PROBE
(RESISTANCE VALUE 10
KOHM AT 77°F (25°C) NTC);
REPLACE IT;
AUTOMATIC.
DISCONNECTED OR WET
PROBE CONNECTOR.
CHECK THE WIRING.
E06
DOMESTIC INLET
TEMP. PROBE
BROKEN OR INCORRECTLY
CALIBRATED PROBE
(RESISTANCE VALUE 10
KOHM AT 77°F (25°C) NTC);
REPLACE IT;
AUTOMATIC.
DISCONNECTED OR WET
PROBE CONNECTOR.
CHECK THE WIRING.
E15
RECIRCULATION
TEMP. PROBE
BROKEN OR INCORRECTLY
CALIBRATED PROBE
(RESISTANCE VALUE 10
KOHM AT 77°F (25°C) NTC);
REPLACE IT;
AUTOMATIC.
DISCONNECTED OR WET
PROBE CONNECTOR.
CHECK THE WIRING.
E16
COMBUSTION
BLOWER
COMBUSTION BLOWER
BOARD BROKEN;
REPLACE IT;
AUTOMATIC.
COMBUSTION BLOWER
BROKEN;
REPLACE IT;
FAULTY POWER SUPPLY
CABLE.
REPLACE IT.
Содержание SFK 55
Страница 6: ......
Страница 32: ......
Страница 61: ...61 SFK 55 RAD ING Manual 1512 2_CSA_TTS 3 USE USER ...
Страница 62: ...62 SFK 55 RAD ING Manual 1512 2_CSA_TTS 3 USE USER ...
Страница 63: ...63 SFK 55 RAD ING Manual 1512 2_CSA_TTS 3 USE USER ...
Страница 64: ...64 SFK 55 RAD ING Manual 1512 2_CSA_TTS 3 USE USER ...
Страница 73: ......
Страница 74: ......
Страница 75: ......